3-5 Converting Projects
3-17
Model before
conversion
Model after
conversion
Screen Size
NSJ12
Base screens will be resized to 800 x 600 dots.
NSJ10
Base screens will be resized to 640 x 480 dots.
NSJ8
Base screens will be resized to 640 x 480 dots.
NSJ5-SQ/TQ
Base screens will be resized to 320 x 240 dots.
NS-Runtime or NSA
NSH5
Base screens will be resized to 320 x 240 dots.
The communications settings of the hosts of the serial port A and B will be changed as
follows.
Before Conversion
After Conversion
Host Type
SYSMAC-CS1/SYSMAC-CJ1/
SYSMAC-CV/SYSMAC-CJ2
SYSMAC-PLC
Host Link
Host Link
Protocol
Toolbus
1:N NT Link
Port Name
COM port
---
19,200 19,200
Comm. Speed (Host Link)
38,400, 57,600, or 115,200
9600
Data Bits (Host Link)
4 bits, 5 bits, 6 bits, 7 bits, 8 or bits
7 bits (fixed)
Stop Bits (Host Link)
1 bit/ 2 bits
2 bits (fixed)
Parity (Host Link)
Even, Odd, None, Mark, or Space
Even (fixed)
Comm. Speed (1:N NT Link)
---
High speed
Unit No. (1:N NT Link)
---
0
N
N
N
o
o
o
t
t
t
e
e
e
The project data will be changed if you specify to convert the model to one of the following models
(if the project to be converted is a version lower than the one given in the following table).
NS model to be converted
Project data version after conversion
NS15 Ver.
8.1
NS5-
@@
1
@
-V2 Ver.
8.0
NSJ5-
@@
1
@
Ver.
8.0
NSH5-
@@
1
@
-V2 Ver.
8.0
After the conversion, check the communications settings and make changes according to the
operating environment. For details on communications settings, refer to information on setting the
system and projects in the online help for the CX-Designer.
When the model is converted to an NS-series PT, the document table settings will be cleared, but
the set PDF files will not be deleted. The PDF files will remain in the project folder and other
specified folders. Delete the PDF files manually if they are not required.
Refer to
4-5 Macros
for information on macros for NS-Runtime.
The model conversion will stop if there are items that cannot be converted to the NS-series PT. If
this occurs, the items that cannot be converted will be displayed in the Output Window. Check the
details, revise the project data so that it can be converted, and then attempt to perform model
conversion again.
Содержание NS-NSRCL Series
Страница 1: ...Cat No V093 E1 05 NS Runtime Software USER S MANUAL...
Страница 2: ......
Страница 28: ...1 4 Comparison between the NS Series and the NS Runtime 1 14...
Страница 38: ...2 6 User Interface 2 10...
Страница 56: ...3 5 Converting Projects 3 18...
Страница 84: ...4 5 Macros 4 28...
Страница 136: ...5 11 Window Size 5 52...
Страница 154: ...7 3 Error Messages and Countermeasures 7 6...
Страница 156: ......
Страница 157: ......