2-3-3 Temperature controller communications settings
This summarizes temperature controller communications settings.
For more details on settings and operation procedure of setting specifications, refer to the
relevant temperature controller manual.
■
E5ZN
Setup Switch on E5ZN panel
Unit number
0 to 15
When using multiple E5ZN units, be
careful not the use the same number
twice.
0 4800
Bps
1 9600
Bps
Baud rate
2 19200
Bps
Communications setting level
CH
Value
Data bits
C3 0013 or
C3 0113
7 7
bits
Stop bits
C3 0014 or
C3 0114
2 2
bits
Parity
C3 0015 or
C3 0115
2 Even
(EvEn)
Response
Waiting time
C3 0016 or
C3 0116
0 to 270FH
( 0 t o
9999)
In ms
■
E5GN/E5AN/E5EN/E5CN/E5ER/E5AR
Adjustment level
L.Adj
on enable
Communications
writing
CoWt
OFF disable
Communications setting level L.S
2.4
4.8
9.6
19.2
Baud rate
bPS
38.4
In kbps
Set all communicating temperature
controllers to match parameters of NS
E5ER/AR: choose between
9.6/19.2/38.4
E5
□
N: 38.4 cannot be selected.
Data bits
LEn
7
7 bits
Stop bits
Sbit
2
2 bits
Parity Prty
EvEn
Even
Response
Waiting time
SdWt
0 to 270FH
( 0 to
9999 )
In ms
E5AR/ER range: 0 to 63H(0 to 99)
Communications
Unit No.
U-no
0 to 31
E5AR/ER only
Protocol select
PSEL
CyF
Compoway/F (E5AR/ER only)