Command Reference: Function Blocks
Section 6-5
6-5-15 Function Block: Counter
Diagram
Default Connections
General Description
This function can be used only in NE1A-series Controllers with unit version
1.0 or later.
The Counter function block counts the input pulses at an input and turns ON
the Output Enable signal when the count reaches a set value (SV) set with the
Network Configurator. The function counts the number of OFF-to-ON transi-
tions in the input signal.
When the input count reaches the preset SV, the Output Enable signal is
turned ON and held ON. To detect pulses in the input signal, the input pulse’s
OFF time and ON time must be longer than the cycle time.
■
Reset Methods (Reset Condition)
The Reset Condition used to reset the input count (PV) can be set to Manual
Reset or Auto Reset.
When the reset condition is set to Auto Reset and the input count reaches the
SV set in the configuration data, the Output Enable signal is turned ON and
remains ON as long as the input signal is ON. When the input signal goes
OFF, the input count is reset.
When the reset condition is set to Manual Reset, the input count is reset and
the Output Enable signal is turned OFF when the Reset signal goes ON. Input
pulses will not be counted while the Reset signal is ON.
■
Counting Methods (Count Type)
The Count Type can be set to Down counter or Up counter (decrementing or
incrementing counter).
With a Down (decrementing) counter, the preset SV is the counter’s initial
value and the counter decrements the count by 1 each time that an input
pulse is detected. The Output Enable signal is turned ON when the count
reaches 0.
This function block’s count PV is stored in the function block’s internal work
area, and can be monitored from a Programming Device.
With an Up (incrementing) counter, the counter’s initial value is 0 and the
counter increments the count by 1 each time that an input pulse is detected.
The Output Enable signal is turned ON when the count reaches the preset SV.
Output Enable
Input
Reset
Содержание NE1A-SCPU01 - 07-2009
Страница 2: ...NE1A Series Safety Network Controller NE1A SCPU01 V1 SCPU02 Operation Manual Revised September 2006...
Страница 3: ...iv...
Страница 9: ...x TABLE OF CONTENTS...
Страница 11: ...xii...
Страница 15: ...xvi...
Страница 33: ...xxxiv Unit Versions of NE1A series Controllers 7 Click the OK Button This completes the procedure...
Страница 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Страница 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Страница 73: ...38 Installation Section 3 1 NE1A SCPU02 Weight Model Weight NE1A SCPU01 V1 460 g max NE1A SCPU02 690 g max...
Страница 85: ...50 Wiring Section 3 2...
Страница 123: ...88 Explicit Message Communications Section 4 7...
Страница 141: ...106 Safety Outputs Section 5 4...
Страница 257: ...222 Connection Status Tables Section 10 8...
Страница 258: ...223 SECTION 11 Maintenance and Inspection 11 1 Inspection 224 11 2 NE1A series Controller Replacement 225...
Страница 261: ...226 NE1A series Controller Replacement Section 11 2...
Страница 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Страница 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Страница 267: ...232 Appendix A Local Output Setting Example...
Страница 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Страница 270: ...235 Appendix A Local Output Setting Example...
Страница 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Страница 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Страница 276: ...241 Appendix A Local Output Setting Example...
Страница 289: ...254...
Страница 293: ...258 Index...