background image

EN-25

FF_CAL



Feed forward motor acceleration time active

• Perform the complete tuning procedure
• Abort the tuning by setting 

n5-05 = 0.

FRL

Ref Missing



No speed was selected before the inverter start.

Check the speed selection/start sequence.

GF

Ground Fault



The ground current at the Inverter output exceeded 
50% of the Inverter rated output current and L8-09=1 
(Enabled).

• Remove the motor and run the Inverter without the 

motor.

• Check the motor for a phase to ground short.
• Check the output current with a clampmeter to ver-

ify the DCCT reading.

• Check the control sequence for wrong motor contac-

tor signals.

LF

Output Phase 

Loss



An open-phase occurred at the Inverter output.
The fault is detected when the output current falls 
below 5% of the inverter rated current and L8-07=1 

• Reset the fault after correcting its cause.
• Check the motor and Inverter capacity.

OC

Over Current



The Inverter’s output current exceeded the over cur-
rent detection level.

• Remove the motor and run the Inverter without the 

motor. 

• Check the motor for a phase-to-phase short.
• Verify the accel/decel times 
• (C1-

††

).

• Check the Inverter for a phase-to-phase short at the 

output.

OH 

Heatsink Over-

temp



L8-03 = 0,1 or 2 and the temperature of the Inverter's 
cooling fin exceeded the L8-02 value. 

• Check for dirt build-up on the fans or heatsink. 
• Reduce the ambient temperature around the drive.
• Replace the cooling fan(s).

Inverter's Cooling Fan Stopped



L8-03 = 3 and the temperature of the Inverter's cool-
ing fin exceeded the L8-02 value. 

OH1

Heatsink Max 

Temp



The temperature of the Inverter’s heatsink exceeded 
105 °C.

• Check for dirt build-up on the fans or heatsink.
• Reduce the ambient temperature around the drive.
• Replace the cooling fan(s).

Inverter’s Cooling Fan Stopped

OL1

Motor Overload



Detected when L1-01 is set to 1,2 or 3 and the 
Inverter’s output current exceeded the motor over-
load curve. 
The overload curve is adjustable using parameter E2-
01 (Motor Rated Current), L1-01 (Motor Protection 
Selection) and L2-02 (Motor Protection Time Con-
stant)

• Recheck the cycle time and the size of the load as 

well as the accel/decel times 

• (C1-

††

).

• Check the V/f characteristics (E1-

††

).

• Check the setting of Motor Rated Current Setting 

(E2-01).

OL2

Inv Overload



The Inverter output current exceeded the Inverter’s 
overload capability.

• Recheck the cycle time and the size of the load as 

well as the accel/decel times

• (C1-

††

).

• Check the V/f characteristics (E1-

††

).

• Check the setting of Motor Rated Current Setting 

(E2-01).

OS

Motor Over speed 

Det



F1-03 = 0, 1 or 2 and A1-02 is set to 3 or 6.
The motor speed feedback (U1-05) exceeded the F1-
08 value for the time F1-09.or longer.

• Adjust the ASR settings in the C5 parameter group.
• Check the reference circuit and reference gain. 
• Check the settings in F1-08 and F1-09.



F1-03 = 3 and A1-02 is set to 3 or 6.
The motor speed feedback (U1-05) exceeded the F1-
08 value for the time F1-09.or longer.

OV

DC Bus Overvolt



(only in 

stop 

condi-

tion)



The DC bus voltage has exceeded the overvoltage 
detection level.
Default detection levels are: 
200 V class: 410 VDC
400 V class: 820 VDC

• Increase the deceleration time (C1-02/04/06/08) or 

connect a braking option.

• Check the power supply and decrease the voltage to 

meet the inverter’s specifications.

• Check the braking chopper / resistor.

PF

Input Phase Loss



Too big DC bus voltage ripple. 
Only detected when L8-05=1 (enabled)

• Tighten the input terminal screws
• Check the power supply voltage

PGO

PG Open

(PG Disconnec-

tion)



F1-02 = 0, 1 or 2 and A1-02 = 3 or 6
No PG (encoder) pulses are received for the time F1-
14 or longer.

• Fix the broken/disconnected wiring.
• Fix the wiring.
• Supply power to the PG 
• properly.
• Check the sequence and if the brake is opened when 

the inverter starts to increase the speed.



F1-02 = 3 and A1-02 = 3 or 6.
No PG (encoder) pulses are received for the time F1-
14 or longer.

 Display

Displayed as

Meaning

Corrective Actions

Alarm

Fault

Содержание L7Z -

Страница 1: ...Quick Start Guide L7Z Cat No I62E EN 01...

Страница 2: ......

Страница 3: ...n 13 Autotuning 14 Autotuning Mode Selection 14 Autotuning Alarms and Faults 15 Autotuning Procedure with Induction Motors 16 Autotuning Procedure for PM Motors 17 PM Motor Encoder Offset Tuning 18 Ri...

Страница 4: ...RC interference suppression filters capacitors or overvoltage protection devices to the inverter input or output To avoid unnecessary over current faults etc being displayed the signaling contacts of...

Страница 5: ...unauthorized persons must not be allowed access to these inverters Keep these Safety Precautions and Instructions for Use readily accessible and supply them to all persons with any form of access to t...

Страница 6: ...is L7 inverter can drive induction motors as well as permanent magnet motors Always select the appropriate control mode For induction motors use V f Open Loop Vector or Closed Loop Vector control A1 0...

Страница 7: ...dance grounding of HF interference The use of grounding straps instead of cables is therefore definitely advisable Moreover cable shields must be connected with purpose made ground clips 3 Laying Cabl...

Страница 8: ...location without excessive oscillation Install the Inverter in a location free from chlorides Install the Inverter in a location free from direct sunlight Installation Orientation Install the Inverter...

Страница 9: ...ter input or a DC reac tor at the DC reactor connection terminals Use a surge absorber or diode for inductive loads near the Inverter Inductive loads include magnetic con tactors electromagnetic relay...

Страница 10: ...d ground Cable shields have to be grounded on both cable ends Main Circuit Terminals Main circuit terminal functions are summarized according to terminal symbols in Table 1 Wire the terminals correctl...

Страница 11: ...ly for analog references 15 V Max current 20 mA A1 Frequency reference 0 to 10 V 100 0 to 10 V 20 k AC Analog reference neutral E G Shield wire optional ground line connection point Dig ital output si...

Страница 12: ...S2 SC IP24V 24V CN5 A1 A3 B1 B3 B2 A2 External Power Supply Sinking Mode NPN S1 S2 SC IP24V 24V CN5 A1 A3 B1 B3 B2 A2 24 VDC Internal Power Supply Sourcing Mode PNP S1 S2 SC IP24V 24V CN5 A1 A3 B1 B3...

Страница 13: ...ax 1A 30VDC max 1A M1 M2 M3 M5 M4 M6 Brake Command Factory setting Contactor Control Factory setting Inverter Ready Factory setting Multi function contact output 250VAC max 1A 30VDC max 1A Analog inpu...

Страница 14: ...ent Key Selects menu items sets parameter numbers and decrements set values Used to move to the previous item or data DATA ENTER Key Enters menus and parameters and set validates parameter changes RUN...

Страница 15: ...rce Analog Input Digital operator b1 02 0 Set up the analog digital I O s in the H1 xx H2 xx and H3 xx parameters Set up the Acceleration Deceleration times C1 xx S Curves Jerk C2 x Make test runs Fin...

Страница 16: ...ode Selection As the first thing after power up one of the four control modes must be selected depending on the machine type The Closed Loop Vector modes require PG feedback cards Table 4 shows the re...

Страница 17: ...p value E2 02 and the no load current E2 03 after the first run with nominal speed Autotuning for Line to Line Resistance T1 01 2 Non rotating autotuning for line to line resistance can be used in V f...

Страница 18: ...tors have to be closed 5 For autotuning the BB and BB1 signals must be ON Inverter must not be in base block condition 6 Confirm that the motor is mechanically fixed and can not move 7 Power is suppli...

Страница 19: ...02 2 3 Yes Enter auto tuning mode and set parameter T1 01 2 Set T1 02 Motor rated power T1 04 Motor rated current Press the UP button until Tuning Ready display appears Set T1 02 Motor rated power T1...

Страница 20: ...wer supply if it is OFF Check parameter n8 35 If EnDat Hiperface is used check the encoder power supply check the CLOCK and DATA signal wiring Switch off the power supply No Yes Does a OPE06 fault occ...

Страница 21: ...nd eliminate the fault source Open the contactors open the base block inputs and close the brake FINISH Is it possible to remove the ropes Does a CPF24 fault occur Balance the car so that it does not...

Страница 22: ...Source Selection The speed reference source can be selected using parameter b1 01 The factory setting is the digital operator b1 01 0 i e the speeds can be selected using digital inputs Speed Selecti...

Страница 23: ...ut the inverter decelerates to the leveling speed d1 17 when the selected speed signal is removed Inspection Speed can not be selected as travel speed To select the leveling speed as travel speed the...

Страница 24: ...f d1 18 is set to 2 and no digital input is set to nominal speed selection the speed reference with speed selection input set is nominal speed d1 09 When the leveling speed signal is set the inverter...

Страница 25: ...eleration time n5 05 must be tuned Motor Acceleration Time Auto Tuning n5 05 Before the n5 02 auto tuning is performed the motor data autotuning and the general setup should have been finished Do the...

Страница 26: ...Increase the gain to improve the responsiveness to the speed reference Decrease the gain if vibrations or oscillations occur 1 The order of giving the UP or DOWN command has no influence 2 n5 01 shoul...

Страница 27: ...04 0 1 or 2 and A1 02 3 or 6 The speed deviation is higher than the F1 10 value for the time F1 11 or longer Reduce the load Lengthen the acceleration time and deceleration time Check the mechanical s...

Страница 28: ...rent exceeded the motor over load curve The overload curve is adjustable using parameter E2 01 Motor Rated Current L1 01 Motor Protection Selection and L2 02 Motor Protection Time Con stant Recheck th...

Страница 29: ...eck the input voltage and the wiring of the input terminals Extend the settings in C1 01 03 05 07 Main Circuit MC Operation Failure No MC response during Inverter operation Replace the Inverter UV2 CT...

Страница 30: ...too high or too low Closed Loop Vector for PM only Check the motor wiring Check the motor rated current input value Reduce or increase the current level for leakage inductance tuning by changing para...

Страница 31: ...al P gain 2 Set the proportional gain 2 and the inte gral time 2 of the speed control loop ASR for the minimum frequency The setting is active only for acceleration C5 04 ASR integral I time 2 C5 06 A...

Страница 32: ...me Param Num Name Description n5 03 Feed forward proportional gain Speed reference response will increase as the setting of n5 03 is increased n5 05 Motor accelera tion time tuning 0 Disabled 1 Enable...

Страница 33: ...Speed agree 1 Inverter ready 1 Minor fault 1 Major fault U2 13 Operation status at fault U2 14 Cumulative operation time at fault Fault History Data U3 01 to U3 04 Last fault to Fourth last fault U3...

Страница 34: ...EN 31...

Отзывы: