K8AK-VS
7
●
Setting Method
1.
Setting Voltage
The voltage knob (SV) is used to set the voltage.
The voltage can be set to 10% to 100% of the maximum setting range.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the voltage.
The maximum setting range will differ depending on the model and the input terminal.
Example: K8AK-VS3 Using Input Terminal V3-COM
The maximum setting range will be 600 VAC/VDC and the setting range will be 60 to 600 V.
2.
Hysteresis
Hysteresis is set using the hysteresis knob (HYS.)
The setting range is 5 to 50% of the operating value.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same
level.)
Use this as a guide to set the hysteresis.
Example: Maximum Setting of 600 VAC/VDC, Voltage Set Value (SV) of 50%, and Overvoltage Operation
Operation will be at 300 V and resetting at 270 V when the hysteresis (HYS.) is set to 10%.
3.
Operating Time
The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the operating time.
If the input voltage exceeds (or drops lower than) the voltage set value, the alarm indicator will start flashing for the set period and then stay lit.
Dimensions
(Unit: mm)
Single-phase Voltage Relays
Optional Parts for DIN Track Mounting
22.5
90
100
72
5
K8AK-VS2
K8AK-VS3
*Dimensions in parentheses are for the PFP-50N.
4.5
15 25
25
10
10
1,000 (500)*
25
25
15 (5)*
35
±0.3
7.3
±0.15
27
±0.15
1
●
DIN Tracks
PFP-100N
PFP-50N