Ratings and Specifications

Ratings

Specifications

Power supply voltage

24 VAC 50/60 Hz  or 24 VDC
100 to 240 VAC 50/60 Hz

Voltage across electrodes

5 V p-p (Approx. 20 Hz)

Power consumption

24 VAC/DC: 2.0 VA/1.1 W max.
100 to 240 VAC: 4.6 VA max.

Operating resistance

10 to 100 k

Ω

 (variable)

Reset resistance

250 k

Ω

 max.

Response time

Approx. 0.1 to 10 s (variable)

Length of cable

100 m max. (fully insulated 3-core 0.75-mm

2

 cab-

tyre cable, 600 V)

Indicators

PWR: Green, RY: Yellow

Output contact ratings

Rated load

Resistive load
5 A at 250 VAC
5 A at 30 VDC

Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 
5 A at 250 VAC or 30 VDC: 50,000 operations
3 A at 250 VAC/30 VDC: 100,000 operations

Ambient operating 
temperature

20 to 60

°

C (with no condensation or icing)

Storage temperature

25 to 65

°

C (with no condensation or icing)

Ambient humidity

25% to 85% (with no condensation)

Storage humidity

25% to 85% (with no condensation)

Altitude

2,000 m max.

Terminal screw 
tightening torque

0.49 to 0.59 N·m

Case color

N1.5

Case material

PC and ABS, UL 94 V-0

Weight

Approx. 150 g

Mounting

Mounts to DIN Track.

Dimensions

22.5 

×

 90 

×

 100 mm (W

×

D

×

H)

Operating voltage 
range

85% to 110% of rated voltage

Installation environ-
ment

Installation category II, pollution level 2

Approved standards

EN 61010-1

EMC

EN 61326-1 Industrial electromagnetic environment

Safety standards

UL 508 (Recognition), 
Korean Radio Waves Act (Act 10564), 
CSA: C22.2 No.14, CCC: GB14048.5

Insulation resistance

20 M

Ω

 min.

Between all external terminals and the case
Between all power supply terminals and all input 
terminals
Between all power supply terminals and all output 
terminals
Between all input terminals and all output termi-
nals

Dielectric strength

2,000 VAC for 1 min

Between all external terminals and the case
Between all power supply terminals and all input 
terminals
Between all power supply terminals and all output 
terminals
Between all input terminals and all output termi-
nals

Noise immunity

1,500 V power supply terminal common/normal 
mode
Square-wave noise of 

±

1-

μ

s/100-ns pulse width with 

1-ns rise time

Vibration resistance

Frequency: 10 to 55 Hz, acceleration 50 m/s

2

10 sweeps of 5 min each in X,Y, and Z directions

Shock resistance

100 m/s

2

, 3 times each in 6 directions along 3 axes

Degree of protection

Terminals: IP20

Содержание K8AK-LS

Страница 1: ...ent information on models that have been certified for safety standards refer to your OMRON website Power supply voltage Model 24 VAC DC K8AK LS1 24 VAC DC 100 to 240 VAC K8AK LS1 100 240 VAC Application For general pur pose use such as water supply lines For areas with limited space For liquids with low resistance When mounting strength is re quired For resistance to high temperature or high pres...

Страница 2: ...color N1 5 Case material PC and ABS UL 94 V 0 Weight Approx 150 g Mounting Mounts to DIN Track Dimensions 22 5 90 100 mm W D H Operating voltage range 85 to 110 of rated voltage Installation environ ment Installation category II pollution level 2 Approved standards EN 61010 1 EMC EN 61326 1 Industrial electromagnetic environment Safety standards UL 508 Recognition Korean Radio Waves Act Act 10564 ...

Страница 3: ...ut 250 VAC 5 A resistive load 30 VDC 5 A resistive load A Water Level Inputs LS1 B Power Supply Voltage 100 to 240 VAC 24 VAC DC No polarity 12 Relay Output Common Water or other liquid Control Output A2 A1 A2 A1 E1 E2 E3 11 14 12 Power supply voltage Water or other liquid E1 E2 E3 A1 A2 A1 A2 12 14 11 L1 L2 L3 Pump motor protection mechanisms have been omitted Source of liquid Motor Pump Three ph...

Страница 4: ...cator turns ON the pump starts When the liquid level falls below E2 indicator turns OFF the pump stops Power supply voltage A1 A2 Electrode terminals E2 E3 Electrode terminals E1 E3 Control output terminals 11 14 operation indication P OFF stop ON start Operation indicator OFF Operation indicator ON E1 E2 E3 Power supply voltage A1 A2 Electrode terminals E2 E3 Electrode terminals E1 E3 Control out...

Страница 5: ...es not have SW2 DIP Switch Function Note All pins are set to OFF by default Operating time knob Power indicator Relay status indicator Operating resistance knob Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 Item Description Power indicator PWR Green Lit when power is being sup plied Relay status indicator RY Yellow Lit when contacts are operating Item Description Operating resi...

Страница 6: ...Conductive Level Controller Optional Parts for DIN Track Mounting 22 5 90 100 72 5 K8AK LS DIN Tracks PFP 100N PFP 50N Dimensions in parentheses are for the PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 ...

Страница 7: ...ecified torque of 0 49 to 0 59 N m Use of the product beyond its life may result in contact welding or burning Make sure to consider the actual operating conditions and use the product within its rated load and electrical life count The life of the output relay varies significantly with the switching capacity and switching conditions CAUTION Indicates a potentially hazardous situation which if not...

Страница 8: ...ke sure the indicators operate correctly Depending on the application environment the indicators may deteriorate prematurely and become difficult to see 15 The terminal blocks may heat up to 65 C Use care when handling them 16 Do not use the product if it is accidentally dropped The internal components may be damaged 17 Be sure you understand the contents of this catalog and handle the product acc...

Страница 9: ...MEMO 9 ...

Страница 10: ...MEMO 10 ...

Страница 11: ... CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity with any standards codes or regulations which apply to the combination of the Product i...

Страница 12: ...S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Tokyo JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA CO LTD Room 2211 Bank of China Tower 200 Yin...

Отзывы: