manualshive.com logo in svg
background image

K8AC-H

14

Settings Method
Settings Methods for SSR and ON/OFF Control Heaters

Settings Conditions

Detecting burnouts in just one heater when ten 300-W rated heaters 
are connected in parallel to a single-phase 200-V power supply. 
The heater is SSR controlled.

Normal Heater Current and Heater Current with One 
Heater Element Burnout

Normal current = (300 W 

×

 10 (heaters))/200 V = 15.0 A

Current with one burnout = (300 W 

×

 9)/200 V = 13.5 A

Heater burnout alarm set value = 

Selecting Heater Element Burnout Detector Models

For the above example, K8AC-H12C

@

-FLK would be selected.

The burnout alarm set value is 14.3 A, so the current input range 2.00 
to 22.00 A should be selected.
SSR control is used, so type C should be selected. (Type C is also 
selected for ON/OFF control.)
Select the appropriate relay or transistor output specifications, 
depending on the application.

K8AC-H Parameter Setting Procedure 

(Only the minimum settings are shown here. Refer to pages 16 to 
18 for information on how t
o set parameters.)

1. Turn ON the power to the K8AC-H. The initial status when power 

is turned ON is called Run Mode.

2. Press the 

L

 Key for at least 3 s to change from Run Mode to 

Adjust Mode (the mode for adjusting burnout alarm set values.)

3. Set the burnout alarm set values. (AL-1 = CT1 burnout alarm set 

value and AL-2 = CT2 burnout alarm set value.)
Set “14.3” to AL-1.
Set the AL-2 burnout alarm set value to “----” so that it will not 
detect heater burnout, because this is a single-phase heater.

4. Change to Run Mode.

Press the

 L

 Key while in Adjust Mode for at least 1 s to change 

to Run Mode.

5. Check operation.

Test heater burnout detection by burning out one heater.
Also check that there are no malfunctions during temperature 
control.

Note: The default setting for functions including the voltage 

fluctuation compensation function, alarm hysteresis, output 
ON-delay time, and SSR error detection function is OFF. Turn 
ON any of these functions as required.

Settings Method for Cyclic and Phase Control Heaters

Settings Conditions

Detecting burnouts in one heater when five 1,000 W-rated heaters are 
connected to each phase of a three-phase delta-connected 200-V 
power supply.
A power regulator (phase control) performs heater control.

Normal Heater Current and Heater Current With One 
Heater Element Burnout

Example: When One of Five Single-phase Heaters (R-S) Burns 
Out
Normal current = 

 (1,000 W 

×

 5 (heaters))/200 V = 43.3 A

Current with one burnout = 43.3 A 

× 

0.91 = 39.4 A

(Refer to Rate of Change for Currents with Parallel Heaters on 
page 10.)

Heater burnout alarm set value = 

Selecting Heater Element Burnout Detector Models

For the above example, K8AC-H13P

@

-FLK would be selected.

The burnout alarm set value is 41.4 A, so the current input range 20.0 
to 200.0 A should be selected.
Phase control is used, so type P should be selected. (Type P is also 
selected for cyclic control.)
Select the appropriate relay or transistor output specifications, 
depending on the application.

K8AC-H Parameter Settings Procedure 

(Only the minimum settings are shown here. Refer to pages 16 to 
18 for in
formation on how to set parameters.)

1. Turn ON the power to the K8AC-H. The initial status when power 

is turned ON is called Run Mode.

2. Press the 

L

 Key for at least 3 s to change from Run Mode to 

Adjust Mode (the mode for adjusting burnout alarm set values.)

3. Change from Adjust Mode to Set Mode (the default settings mode 

for all functions). The password “0169” is required to move to Set 
Mode.

4. Set the heater control method parameter to PH-3 (three-phase 

control).
The default setting is PH-1 (single-phase control).
Note: Set the parameter to CYCL (cyclic control) when using 

cyclic control.

5. Press the 

L

 Key for at least 1 s to change from Set Mode to Adjust 

Mode. Press the 

L

 Key again for at least 1 s to change from 

Adjust Mode to Run Mode.

Note: The default setting for functions including the voltage 

fluctuation compensation function, alarm hysteresis, output 

ON-delay time, and SSR error detection function is OFF. Turn 
ON any of these functions as required.

Burnout Alarm Set Value Setting Method
Setting Method

Wire the K8AC-H, temperature controller (4 to 20 mA current 
output type), and power regulator (phase control).

Press the 

L

 Key on the K8AC-H for at least 3 s to change from 

Run Mode to Adjust Mode.

AL-1 (CT1 burnout alarm set value) will be displayed when the 
mode is changed to Adjust Mode. Press the 

S

 key once when AL-

1 is displayed. Next, press the 

U

 Key once. The present heater 

current value will be displayed on the main display, so note this as 
the normal current value. Always have the temperature controller 
output at 20.0 mA at this time (See note 1.)

Next, disconnect one heater and note the heater current in this 
burnout state. Alternatively, use the current when one heater is 
burned out (calculated earlier) as the current during malfunction. It 
is recommended that the current at an actual burnout is confirmed.

Set the K8AC-H burnout alarm set value based on the results. The 
burnout alarm set value is set at the mid-point between the normal 
current and the current at malfunction, taking errors and variations 
in heater capacity into consideration.

In this setting example, the set value for AL-2 (CT2 burnout alarm 
setting) is the same as the set value for AL-1. (See note 2.)

Note: 1. The K8AC-H automatically adjusts burnout alarm levels to 

compensate based on the temperature controller current 
output. The burnout alarm value must be set when the 
temperature controller output is at 100% (20 mA), so be 
sure to have the temperature controller at 20 mA output.

2. If the heater capacity is unbalanced, the burnout alarm 

values for CT1 and CT2 may not be the same.

(Normal c current at malfunction)

=

15.0 + 13.5

= 14.3 A

2

2

Normal c current at malfunction

=

43.3 + 39.4

=

41.4 A

2

2

3

Содержание K8AC-H2

Страница 1: ...different heater capacities Using heaters with varying heater resistance e g halogen heaters Features High precision Heater Burnout Alarms with High resolution Digital Measurement Burnout Alarm Possi...

Страница 2: ...e linked with the control output value from the temperature controller Compatible with Gradient Settings of Power Controllers When using gradient settings with a power controller set a gate current le...

Страница 3: ...tput specifi cations Com munica tions output Current input range 0 200 to 2 200 A 2 00 to 22 00 A 20 0 to 200 0 A 100 to 240 VAC ON OFF control SSR control Two current inputs for either single phase o...

Страница 4: ...200 ms min Input impedance 4 k min Cyclic and phase con trol 4 to 20 mA DC Burnout detection is possible for an input of 7 mA or greater Input impedance 50 max Outputs Relay contact outputs K8AC H C...

Страница 5: ...inals CT primary terminals and gate input terminals communications terminals Between power supply terminals CT primary terminals and output terminals Between gate input terminal communications termina...

Страница 6: ...VAC 0 3 A 30 VDC 1 A Maximum contact voltage 125 VAC 60 VDC Maximum contact current 1 A Maximum switching capaci ty 37 5 VA 30 W Minimum applicable load failure rate P value refer ence value 5 VDC 10...

Страница 7: ...ct to the operating power supply All models 3 to 4 5 to 6 Outputs Outputs SSR open or short circuit detection results Outputs heater burnout or layer short circuit detection results K8AC H2 N transist...

Страница 8: ...CTs for three phase heaters For three phase heaters always set the burnout alarm set values for both CT1 and CT2 5 6 3 4 Transistor Output K8AC H2 N FLK CT2 CT1 3 7 8 9 10 11 12 13 14 1 2 RS 485 X 4 5...

Страница 9: ...Transistor Output K8AC H2 N FLK Heater Power supply Power Regulator Temperature Controller 4 to 20 mA current output Operation Description If the heater current detected at either CT1 or CT2 falls bel...

Страница 10: ...o after one heater burns out with the current prior to the burnout i e the normal current taken as 1 3 In actual operation there may be effects from factors such as load heater imbalances so conduct a...

Страница 11: ...m is output accordingly SSR Short Circuit Detection If current is measured when there is no gate input an SSR short circuit error is detected and an alarm is output SSR Open Circuit Detection If curre...

Страница 12: ...Short Open Circuit Alarm Using the Power Regulator s Gradient Settings The power regulator s gradient settings can be used to prevent malfunction by setting the operation gate current level The relati...

Страница 13: ...urs open or short circuit OFF when SSR is normal ALM Alarm Lights for heater burnout or overcurrent OFF at all other times Up key Increments a set value when the set value is in change status Down key...

Страница 14: ...pe P should be selected Type P is also selected for cyclic control Select the appropriate relay or transistor output specifications depending on the application K8AC H Parameter Settings Procedure Onl...

Страница 15: ...open and short circuits and heater layer shorts The count is refreshed each time an alarm is output and it is saved in non volatile memory The value is saved when power is interrupted The number of o...

Страница 16: ...r at least 1s Press the L key for at least 1 s Press the S key for at least 1 s Press the L key for at least 1s When the key is released Press the S key for at least 1 s Press the L and M keys Press t...

Страница 17: ...etting value 1 Heater layer short circuit detection function SSR open circuit detection function SSR short circuit detection function Output ON delay time Soft startup time Startup lock time Gate inpu...

Страница 18: ...ction function ON and OFF ssht ON OFF OFF SSR Open Circuit Detection Turns the SSR open circuit detection function ON and OFF sopn ON OFF OFF Heater Layer Short Circuit Detection Overcurrent Detection...

Страница 19: ...following torque Power supply terminals 0 5 N m I O terminals 0 23 N m 35 2 1 1 7 4 5 6 100 90 K8AC H2 FLK To remove a wire insert the recom mended flat blade screwdriver straight into the hole under...

Страница 20: ...ories with K8AC CT20L Connection Example Contact Approx 3 dia 18 22 Approx 6 dia Plug Contact Lead Plug 100 15 30 30 5 Two M3 Depth 4 max 12 dia 40 40 5 15 Current Transformer K8AC CT200 Pre wired Lea...

Страница 21: ...se unintended operation and may result in accident or corruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the pr...

Страница 22: ...he current measurement value with the heater output at 100 This is because the burnout detection alarm of the K8AC H P FLK depends on the control input When you set the burnout alarm value make sure t...

Отзывы: