Three-phase Phase-sequence Phase-loss Relay

 

K8AB-PM

Cat. No. N146-E1-02

Safety Precautions

Precautions for Safe Use

Make sure to follow the instructions below to ensure safety.

1.

Do not use or keep this product in the following environments.

Outdoors, or places subject to direct sunlight or wearing 
weather.

Places where dust, iron powder, or corrosive gases (in 
particular, sulfuric or ammonia gas) exist.

Places subject to static electricity or inductive noise.

Places where water or oil come in contact with the product.

2.

Make sure to install this product in the correct direction.

3.

There is a remote risk of electric shock. Do not touch terminals 
while electricity is being supplied.

4.

Make sure to thoroughly understand all instructions in the 
Instructions Manual before handling this product.

5.

Make sure to confirm terminal makings and polarity for correct 
wiring.

6.

Tighten terminal screws firmly using the following torque.
Recommended tightening torque: 0.49 N·m
Maximum tightening torque: 

0.54 N·m max.

7.

Operating ambient temperature and humidity for this product 
must be within the indicated rating when using this product.

8.

There is a remote risk of explosion. Do not use this product where 
flammable or explosive gas exists.

9.

Make sure that no weight rests on the product after installation.

10.

To enable an operator to turn off this product easily, install 
switches or circuit breakers that conform to relevant requirements 
of IEC60947-1 and IEC60947-3, and label them appropriately.

Precautions for Correct Use

For Proper Use

1.

Do not use the product in the following locations.

Places subject to radiant heat from heat generating devices.

Places subject to vibrations or physical shocks.

2.

Make sure to use setting values appropriate for the controlled 
object. Failure to do so can cause unintended operation, and may 
result in accident or corruption of the product.

3.

Do not use thinner or similar solvent for cleaning. Use commercial 
alcohol.

4.

When discarding, properly dispose of the product as industrial 
waste.

5.

Only use this product within a board whose structure allows no 
possibility for fire to escape.

About Installation

1.

When wiring, use only recommended crimp terminals.

2.

Do not block areas around the product for proper dissipation of 
heat. (If you do not secure space for heat dissipation, life cycle of 
the product will be compromised.)

3.

To avoid electrical shocks, make sure that power is not supplied to 
the product while wiring.

4.

To avoid electrical shocks, make sure that power is not supplied to 
the product when performing DIP switch settings.

Noise Countermeasures

1.

Do not install the product near devices generating strong high 
frequency waves or surges.

2.

When using a noise filter, check the voltage and current and 
install it as close to the product as possible.

3.

In order to prevent inductive noise, wire the lines connected to the 
product separately from power lines carrying high voltages or 
currents. Do not wire in parallel with or on the same cable as 
power lines. 
Other measures for reducing noise include running lines along 
separate ducts and using shield lines.

To avoid faulty operations, 
malfunctions, or failure, observe the 
following operating instructions.

1.

When turning on the power, make sure to realize rated voltage 
within 1 second from the time of first supply of electricity.

2.

Make sure to use power supply for operations, inputs, and 
transformer with the appropriate capacity and rated burden.

3.

Maintenance and handling of this product may only be performed 
by qualified personnel.

4.

Distortion ratio of input wave forms must be 30% or less. Use of 
this product with circuits that have large distortion in wave forms 
may result in unwanted operations.

5.

Using this product for thyristor controls or inverters will result in 
errors.

6.

When setting the volume, adjust the control from the minimum 
side to the maximum side.

Содержание K8AB-PM Series

Страница 1: ...Legend 1 Basic Model K8AB Measuring and Monitoring Relays 2 Functions PM Three phase Phase sequence Phase loss Relay Simultaneous upper and lower monitoring 3 Rated Input Voltage 1 115 127 133 138 20...

Страница 2: ...oss 0 1 s max Startup lock time LOCK 1 s or 5 s Switched using DIP switch Indicators Power PWR Green Relay output RY Yellow OVER UNDER Red Output relays Two SPDT relays NC operation Output relay ratin...

Страница 3: ...time Fluctuation based on measured value at standard temperature 20 C to standard temperature 10 max Standard temperature to 60 C 10 max Humidity 25 to 80 Humidity influence Operating value Based on a...

Страница 4: ...L1 L2 L3 T T Note 1 The K8AB PM output relay is normally operative 2 The power ON lock prevents unnecessary alarms from being generated during the instable period when the power is first turned on Th...

Страница 5: ...or Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 0 1 Item Meaning Power indicator PWR Green Lit when power is being supplied see note Relay status indicator RY Yellow Lit when rela...

Страница 6: ...ch Settings The power ON lock time number of wires and rated voltage are set using the DIP switch located on the bottom of the Unit Load Voltage input Signal output 14 12 L1 L2 L3 11 L1 N L2 L3 Signal...

Страница 7: ...urn the knob while there is an input to the input terminals until the alarm indicator flashes when the set value and the input have reached the same level Use this as a guide to set the voltage The ra...

Страница 8: ...in accident or corruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use th...

Страница 9: ...just the slide resistor so that the voltage applied to the K8AB terminals is 120 of the set value for overvoltage detection and 80 of the set value for undervoltage detection when the auxiliary relay...

Страница 10: ...operation As the graph shows phase loss cannot be detected because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light To detect motor load...

Страница 11: ...Cat No N146 E1 02 Three phase Phase sequence Phase loss Relay K8AB PM 11...

Страница 12: ...TIAL DAMAGES LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED ON CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY In no event shall the responsibil...

Отзывы: