Changing the Batch Count Set Value

1. Press the BATCH key to switch from the present value

display to the batch count display.

2. Change the set value when the counter is set to the batch

count display.
• Nonsignificant zeros are normally not shown on the

batch count set value display.

• Press the DISPLAY key to switch back from the batch

count display to the present value display.

Set Mode

Changing Settings in the Set Mode

1. Press the MODE key to switch from run mode to set mode.

• The counter will continue operation if switched from

run mode to set mode during operation.

• The MODE key will be locked if the key protect

function is enabled.

• Settings changed in the set mode do not become

effective until the run mode is entered. Because the
operating conditions change once this occurs, always
use the RESET key or a reset input to reset operation.

2. Press the MODE key to scroll successively through the items

that can be set. Release the MODE key to select the desired
item.

3. Changing the selected item:

• Press the MODE key until the desired item appears.
• Change the item setting by pressing keys 1 through 6.

(Press the DISPLAY key to switch back from set
mode to run mode.)

• Press the DISPLAY key to return to run mode from

set mode.

Содержание H7BR Series

Страница 1: ...resets One Two Non independent Input type No voltage Voltage No voltage Voltage Contact and sink NPN H7BR B H7BR BV H7BR BW H7BR BWV transistor outputs Contact and source PNP H7BR BP H7BR BVP H7BR BWP H7BR BWVP transistor outputs Supply voltages 100 to 240 VAC 50 60 Hz or 24 VAC 12 to 24 VDC STANDARD COUNTERS Number of presets One Two Non independent Input type No voltage Voltage No voltage Voltag...

Страница 2: ...t Yes Scaling function 0 001 to 99 999 Sensor power supply 12 or 24 VDC selectable Input signals Batch count reset key protect gate Compensation reset key protect gate Input method No voltage input Via opening and closing of contact Voltage input Via high and low signal voltage key protection is no voltage input Control outputs Single preset models One SPST NO contact and transistor NPN or PNP ope...

Страница 3: ...max 24 VDC 80 mA 10 5 ripple max Approvals UL CSA CE EMC Ambient operating temperature 10 to 55 C 14 to 131 F with no icing Storage temperature 25 to 65 C 13 to 149 F with no icing Ambient operating humidity 35 to 85 RH RATINGS Output Description Applicable mode Single preset counter Double preset counter counter series N Sustained output Sustained output 2 selectable sustained or one shot output ...

Страница 4: ...to 55 Hz with 0 75 mm 0 03 in single amplitude 55 to 150 Hz with 10 G 32 minutes each in three directions Malfunction durability 10 to 55 Hz with 0 5 mm 0 02 in single amplitude 55 to 150 Hz with 10 G 32 minutes each in three directions Shock Mechanical durability Approx 30 G Malfunction durability Approx 10 G Service life Mechanical 10 million operations min Electrical 100 000 operations min at 5...

Страница 5: ...unt CP1 CP2 Count Count input CP1 Gate input CP2 Count Count Count input CP1 Count Down Count INPUT MODES Up H L H L Gate input CP2 0 0 1 2 3 4 5 H L H L 0 0 1 2 3 4 5 H L H L 0 n n 1 n 2 n 3 n 4 n 5 Count input CP2 Gate input CP1 H L H L 0 n 5 n 4 n 3 n 2 n 1 n A A H L CP2 H L 0 3 2 1 2 1 2 3 H L H L 0 1 2 3 2 1 1 2 3 H L H L 0 3 2 1 2 1 2 3 Counting speeds of CP1 and CP2 must be the same for Rev...

Страница 6: ...ersible A B and C Output Mode C Present value is placed in reset start status as soon as preset count is reached the preset is not actually displayed Outputs are one shot and operate repeatedly Output 1 latches ON and goes OFF after expiration of the one shot period for Output 2 One shot time periods for Output 1 and 2 are independent Up Down Reversible A B and C One shot output from Output 1 Sust...

Страница 7: ...ut 2 Sustained output Up Down Reversible A B and C Output Mode K Present value runs continuously Output 1 latches ON at preset 1 and goes OFF after expiration of the one shot period for Output 2 One shot time periods for Output 1 and 2 are independent Output Mode R Present value display returns to reset start status after expiration of one shot time period Outputs are one shot and operate repeated...

Страница 8: ...put One shot outputs can be set to 10 50 100 200 500 or 1 000 ms One shot output from Output 2 Sustained output Output Mode Q Present value runs continuously through one shot time period and returns to reset start status immediately afterward Outputs are one shot and operate repeatedly Output 1 latches ON at preset 2 and goes OFF after expiration of the one shot period for Output 2 One shot time p...

Страница 9: ...henever present value is equal to preset 2 Output Mode D Present value increments and decrements within the display s range Output 1 is ON whenever present value is equal to preset 1 Output 2 is ON whenever present value is equal to preset 2 Reversible A B and C Comp Reset 999 999 Comp Preset 2 Preset 1 0 999 999 Output 1 Output 2 Comp Reset 999 999 Comp Preset 2 Preset 1 0 999 999 Output 1 Output...

Страница 10: ...to a value less than the present batch count The batch output will remain ON if the batch preset is changed from a value less than the present batch count to a value greater than the present batch count Notes Counting inputs are not acknowledged while the reset input is ON The compensation input is valid only when the present value is being incremented One shot outputs when ON are turned OFF when ...

Страница 11: ...is from 1 to 5 mm 0 039 to 0 197 in Y92A 72F1 Soft Plastic Cover 72 2 83 72 2 83 100 3 94 67 6 2 66 100 3 94 6 0 24 7 0 28 ACCESSORIES 75 8 2 98 75 8 2 98 Y92A 72T Terminal Cover The terminal cover protects the wiring connections 69 2 72 69 2 72 Two mounting clips help the soft plastic cover Y92A 72F1 fit snugly over the front of the timer to protect against dirt and water Timer settings can be ch...

Страница 12: ...2 to 24 VDC 18 OUT 2 OUT 1 15 16 Key protection input Batch count reset 100 to 240 VAC 24 VAC 12 to 24 VDC 17 Batch Batch Reset input CP2 input 12 14 8 9 11 13 Gate input CP1 input Output common 12 24 VDC OUT 1 16 Key protection input Batch count reset 15 17 1 2 3 4 5 7 6 100 to 240 VAC 24 VAC 12 to 24 VDC 18 OUT 2 Batch OUT 2 OUT 1 OUT 1 OUT 2 CP2 input 0 V 8 9 10 11 12 14 13 Reset input CP1 inpu...

Страница 13: ...level input Transistor ON Residual voltage 2 V max Impedance when ON 1 kΩ max 2 Low level Transistor OFF Impedance when OFF 100 kΩ max Contact Use contacts that can adequately input switch 2 mA at 5 V Voltage inputs Solid state Input NPN Transistor Contact Input Sensor Input use 0 V CP1 CP2 reset etc 12 24 VDC V High transistor OFF Sensor V High transistor ON Input use 0 V CP1 CP2 reset etc 12 24 ...

Страница 14: ...ter height 12 mm zeros suppressed Key name Operation Increment keys 1 6 Used to change the corresponding digit of the set value also used to change data in the set mode Code key Changes code of set value On H7BR C type only Display key Switches to the batch count teaching mode setting displays For double preset model changes the displayed preset value 1 and 2 during operation Batch key Switches to...

Страница 15: ... applicable Batch count preset 0 Not applicable Input mode Up Reversible C phase difference Output mode N K Output 2 time Hold 1 000 ms Output 1 time 2 stage only Hold 1 000 ms CP1 and CP2 counting speeds 30 cps 30 cps Min reset time 20 ms 20 ms Decimal point Far right no fractions Far right no fractions Scale factor 1 000 1 000 Compensation Not applicable 0 Key protection level KP 1 KP 1 although...

Страница 16: ...ACH key Press the DISPLAY key Press the MODE key Press the DISPLAY key Set mode Input mode Press the MODE key Output mode Output 2 time Output 1 time CP1 count speed CP2 count speed Min reset time Decimal point Prescale value Compensation count value Key protection level Press the MODE key Press the MODE key Press the MODE key Press the MODE key Press the MODE key Press the MODE key Press the MODE...

Страница 17: ...time Applicable to output modes C R K P Q and A only Output time 1 Yes Yes Determines the output Press keys 1 to 6 to change the displayed mode double time of the control out preset model put OUT 1 for double only preset model counters H7BR BW only Applicable to output modes C R K P Q and A only CP1 CP2 Yes Yes Switches the count input Press keys 1 to 6 to change the displayed mode count speed fil...

Страница 18: ...m on the right Teaching Prescale No Yes Press TEACH key to set prescale value mode value automatically Set value 1 No Yes Press TEACH key to set present value as double pre the set value set model only Set value 2 No Yes Note 1 Changes made in set mode become effective when run mode is entered 2 The control output is inhibited in the teaching mode 3 The TEACH key and the teaching function do not o...

Страница 19: ...operation if switched from run mode to set mode during operation The MODE key will be locked if the key protect function is enabled Settings changed in the set mode do not become effective until the run mode is entered Because the operating conditions change once this occurs always use the RESET key or a reset input to reset operation 2 Press the MODE key to scroll successively through the items t...

Страница 20: ...the increment keys 1 to 6 Displays 0 when pressing one key from the increment keys 3 Input the count signal of the converted value from external sensor The display to the right indicates that the controlled object has been moved 10 cm causing 50 counts to be input from an external sensor 4 Press TEACH key to set the set value Set value 0 2 10cm 50 If the value input in example 3 is negative the pr...

Страница 21: ...th compensation input Permissible limits of count speed Up to 505 over setting e g 50 cps for Limited to 10 max over setting 30 cps counting speed One shot output time Approximately 0 1 to 1 s 10 to 1 000 ms Contact form of single preset models SPDT SPST NO Precautions REPLACING AN H7AN WITH AN H7BR EXTERNAL POWER SUPPLY The capacity of the power supply from the counter is 160 mA at 12 V or 80 mA ...

Страница 22: ...ut is produced The delay is the result of output control time signal transmission time relay switching time etc Actual measurements in N and K modes Control output Max counting Output delay speed Contact output 30 cps 18 to 24 ms 1 2 1 kcps 4 7 to 5 8 ms 5 kcps 4 4 to 5 4 ms 10 kcps 4 3 to 5 3 ms Transistor output 30 cps 13 5 to 20 ms 1 2 1 kcps 0 59 to 0 81 ms 5 kcps 0 29 to 0 44 ms 10 kcps 0 24 ...

Отзывы: