Single-phase Solid State Relays for Heaters

   

G3PE

453

Relationship between the G3PE and Ducts or Other
Objects Blocking Airflow

Ventilation Outside the Control Panel

Note: 1.

If the air inlet or air outlet has a filter, clean the filter regularly
to prevent it from clogging to ensure an efficient flow of air.

2.

Do not locate any objects around the air inlet or air outlet,
otherwise the objects may obstruct the proper ventilation of
the control panel.

3.

A heat exchanger, if used, should be located in front of the
G3PE to ensure the efficiency of the heat exchanger.

G3PE Ambient Temperature

15A and 25A models have ambient temperature of 40

°

C, while 35A

and 45A models have 25

°

C ambient Temperature. The G3PE uses a

semiconductor to switch the load. This causes the temperature inside
the control panel to increase due to heating resulting from the flow of
electrical current through the load. The G3PE reliability can be
increased by adding a ventilation fan to the control panel to dispel
this heat, thus lowering the ambient temperature of the G3PE.
(Arrhenius's law suggests that life expectancy is doubled by each
10

°

C reduction in ambient temperature.)

Example: For 10 G3PE SSRs with load currents of 15 A, 

0.23 

×

 10 = 2.3

Thus, 3 fans would be required.

Note: 1.

Size of fans: 92 mm 

×

 92 mm, Air volume: 0.7 m

3

/min, 

Ambient temperature of control panel: 30

°

C

2.

If there are other instruments that generate heat in the 
control panel in addition to SSRs, more ventilation will be re-
quired.

3.

Ambient temperature: The temperature that will allow the
SSR to cool by convection or other means.

SSR rated current (A)

15 A

25 A

35 A

45 A

Required number of 
fans per SSR

0.23

0.39

0.54

0.70

Duct or other object 
blocking airflow

Duct

Duct

Duct

Duct

Duct

Vertical
Direction

50 mm max.

Airflow

Base

SSR

SSR

SSR

Incorrect Example

Countermeasure 1

Countermeasure 2

Mounting surf

ace

Mounting surf

ace

Mounting surf

ace

If the depth direction of 
the G3PE is obstructed by 
ducts, the heat radiation 
will be adversely affected.

(No more 
than 1/2 
the SSR 
depth is 
recom-
mended.) 

Use ducts that have a 
shallow depth, to provide 
a sufficient ventilation 
area. 

If the ducts cannot be made 
lower, place the G3PE on a 
metal base so that it is not 
surrounded by the ducts.

SSR

Air inlet

Be aware of airflow

Ventilation
outlet
(Axial Fan)

SSR

SSR

Duct or other object blocking airflow

Содержание G3PE Series

Страница 1: ...els The applicable load current depends on the ambient temperature For details refer to Load Current vs Ambient Temperature in the Engineering Data section Refer to Safety Precautions Number of phases...

Страница 2: ...1 cycle 440 A 60 Hz 1 cycle Permissible I2 t reference value 121A2 s 260A2 s 1 260A2 s Applicable load resistive load 3 kW at 200 VAC 5 kW at 200 VAC 7 kW at 200 VAC 9 kW at 200 VAC Model G3PE 215B G...

Страница 3: ...3PE 245B L 30 25 20 15 10 7 0 Load current A 30 20 0 20 40 60 80 100 Ambient temperature C G3PE 25B L G3PE 15B L 30 20 0 20 40 60 80 100 18 17 14 25 50 45 40 35 30 20 10 0 G3PE 245B L G3PE 235B L Load...

Страница 4: ...0 20 40 60 80 100 Ambient temperature C Load current A 5 7 20 15 13 12 10 5 0 3 Relays 8 Relays 40 20 0 20 40 60 80 100 8 30 25 20 19 15 5 10 7 0 Ambient temperature C Load current A 8 Relays 3 Relays...

Страница 5: ...Diagram Output side t i u c r i c r e g g i r T Input side t i u c r i c t u p n I 1 2 A1 A2 G3PE 2 B Input side Output side t i u c r i c r e g g i r T t i u c r i c t u p n I 68 13 5 6 Two M5 Two M3...

Страница 6: ...G3PE may result in shorting failures of the output elements or burn damage Do not use the G3PE if the heat radiation fins have been bent by being dropped Doing so may result in malfunction due to a r...

Страница 7: ...mounted horizontally For details on close mounting refer to the related information under performance characteristics Mount the G3PE in a direction so that the markings read natu rally Wiring When usi...

Страница 8: ...Mounting Models with Externally Attached Heat Sinks Before attaching an external Heat Sink or Radiator to the Unit always apply silicone grease such as Toshiba Silicone s YG6260 or Sinetsu Silicone s...

Страница 9: ...uggests that life expectancy is doubled by each 10 C reduction in ambient temperature Example For 10 G3PE SSRs with load currents of 15 A 0 23 10 2 3 Thus 3 fans would be required Note 1 Size of fans...

Страница 10: ...umburg IL 60173 847 882 2288 09 11 Specifications subject to change without notice All sales are subject to Omron Electronic Components LLC standard terms and conditions of sale which can be found at...

Отзывы: