5

Operation

Replacement Parts

G32A-A Power Device Cartridge

The G32A-A Power Device Cartridge (a Triac Unit) can be replaced with a new one. When the temperature indicator has changed from pink to red, 
the triac circuitry may have malfunctioned possibly by an excessive flow of current, in which case, dismount the damaged cartridge for replacement.

The damaged cartridge can be replaced with a new one without disconnecting the wires from the G3PA.

Improve the heat radiation efficiency of the G3PA before replacing the cartridge.

The G32A-A Power Device Cartridge can withstand an excessive current for a short period of time, such as may be caused accidentally by the 
short circuitry of the load, in which case the temperature indicator will not turn red.

Be sure to turn OFF the power supply when replacing the Cartridge. Supplying power with the Cartridge removed may result in malfunction.

To remove or replace the Power Device Cartridge for the G3PA-210B-VD, G3PA-220B-VD, or G3PA-420B-VD(-2), use the special tool provided 
with it for extraction. (No special tool is required for other models.) 

The G3PA can be broadly divided into two series: Previous models and models with model numbers that end with "-VD." The Cartridge shown at 
the right cannot be mounted to models in the G3PA-

@@@

B-(-US) Series.

Appearance

Replacing Power Device Cartridges

When replacing Power Device Cartridges, use the specified model. Using a Power Device Cartridge other than the specified one will result in faulty 
operation and destruction of the elements.

G32A-A10(L)-VD G32A-A20(L)-VD

G32A-A40(L)-VD

G32A-A60(L)-VD

G32A-A420-VD(-2)

G32A-A430-VD(-2)

G32A-A450-VD-2

Содержание G3PA

Страница 1: ...nd VDE reinforced insulation Refer to Safety Precautions for All Solid State Relays For the most recent information on models that have been certified for safety standards refer to your OMRON website...

Страница 2: ...430B VD 2 30 A at 200 to 480 VAC G3PA 450B VD 2 50 A at 200 to 480 VAC Name Carry current Load voltage range Model Applicable SSR VDE certification Power Device Cartridge 10 A 19 to 264 VAC G32A A10 V...

Страница 3: ...1 VDC min G3PA 430B VD G3PA 420B VD 2 G3PA 430B VD 2 G3PA 450B VD 2 Model Rated load voltage Load voltage range Load current Inrush current VDRM reference value G3PA 210B L VD 24 to 240 VAC 50 60 Hz...

Страница 4: ...s 1 800 A2 s 1 800 A2 s Insulation resistance 100 M min at 500 VDC Dielectric strength 4 000 VAC 50 60 Hz for 1 min Vibration resistance Destruction 10 to 55 to 10 Hz 0 375 mm single amplitude Mounted...

Страница 5: ...the temperature indicator will not turn red Be sure to turn OFF the power supply when replacing the Cartridge Supplying power with the Cartridge removed may result in malfunction To remove or replace...

Страница 6: ...he letters on the cartridge and those on the G3PA are in the same direction and side A and side B are even 4 Attach the terminal cover 5 Switch on the power and check the G3PA to be sure it works prop...

Страница 7: ...ert the linking terminal securely into the center of the screw and tighten the screw SSR G32A Unit SSR G32A Unit The cover will not fit if the terminal protrudes 1 When SSR are close mounted loosen th...

Страница 8: ...0 20 30 60 40 25 20 80 Panel Ground Ambient temperature C Ambient temperature C Ambient temperature C Load current A Load current A Load current A Vertical Mounting G3PA 240B L VD G3PA 260B L VD G3PA...

Страница 9: ...Input impedance k Input impedance k 40 60 80 100 20 0 20 30 60 40 42 20 3 5 11 28 15 11 14 18 20 10 5 5 5 10 7 Panel Ground Horizontal Mounting Ambient temperature C Ambient temperature C Ambient tem...

Страница 10: ...430B VD 2 Load current A Ambient temperature C Load current A G3PA 420B VD G3PA 420B VD 2 DIN track Panel Ground Close Mounting Up to Three Ambient temperature C Ambient temperature C Ambient temperat...

Страница 11: ...e rated value if it occurs repetitively G3PA 210B L VD G3PA 220B L VD G3PA 420B VD G3PA 420B VD 2 G3PA 240B L VD 260B L VD G3PA 430B VD G3PA 430B VD 2 G3PA 450B VD 2 Inrush current A Peak Energized ti...

Страница 12: ...ircuit Two 4 5 dia or M4 holes 4 6 dia Two M4 100 max G3PA 220B L VD Mounting Holes Without Terminal Cover With Terminal Cover Linking terminal B1 Two M3 5 Linking terminal B2 4 6 x 5 6 elliptical hol...

Страница 13: ...5 4 6 dia 37 max 4 5 x 5 6 elliptic hole 100 max G3PA 420B VD G3PA 420B VD 2 Mounting Holes Terminal Arrangement Internal Connections Trigger circuit Input circuit 100 max Linking terminal B2 Linking...

Страница 14: ...age according to EN55011 The G3PA VD complies with EN55011 standards when a capacitor is connected to the load power supply as shown in the following circuit diagram Recommended Capacitor 1 F 250 VAC...

Страница 15: ...rrents of 20 A 0 31 x 10 3 1 Thus 4 fans would be required Size of fans 92 mm2 Air volume 0 7 m3 min Ambient temperature of control panel 30 C If there are other instruments that generate heat in the...