manualshive.com logo in svg
background image

Solid State Relays

 

G3NH

199

Specifications

Ratings (at an Ambient Temperature of 25

°

C)

Input

*G3NH converts the input current into a constant current.

Output

Note: The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data for 

details.

Characteristics

Rated voltage

Operating voltage

Impedance

(Input current)

Voltage level

Must operate voltage

Must release voltage

5 to 24 VDC

4 to 30 VDC

5 mA max.* 

4 VDC max.

1 VDC min.

100 to 240 VAC

75 to 264 VAC

41 k

Ω±

20%

75 VAC max.

20 VAC min.

Model

Applicable load

Rated load voltage

Load voltage range

Load current 

(See note.)

Inrush current

G3NH-2075B

100 to 240 VAC

75 to 264 VAC

1 to 75 A

800 A 
(60 Hz, 1 cycle)

G3NH-4075B

180 to 440 VAC

150 to 484 VAC

G3NH-2150B

100 to 240 VAC

75 to 264 VAC

1 to 150 A

1,800 A 
(60 Hz, 1 cycle)

G3NH-4150B

180 to 440 VAC

150 to 484 VAC

Item

G3NH-2075B

G3NH-4075B

G3NH-2150B

G3NH-4150B

Operate time

1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)

Release time

1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)

Output ON voltage drop

1.6 V (RMS) max.

Leakage current

30 mA max.
(at 200 VAC)

60 mA max.
(at 400 VAC)

30 mA max.
(at 200 VAC)

60 mA max.
(at 400 VAC)

Insulation resistance

100 M

 min. (at 500 VDC)

Dielectric strength

2,500 VAC, 50/60 Hz for 1 min

Vibration resistance

Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude

Shock resistance

Destruction: 500 m/s

2

Ambient temperature

Operating: –30

°

C to 80

°

C (with no icing or condensation)

Storage:

–30

°

C to 100

°

C (with no icing or condensation)

Ambient humidity

Operating: 45% to 85%

Weight

Approx. 1.8 kg

Approx. 3.0 kg

Содержание G3NH

Страница 1: ...State Relay 2 Rated Load Power Supply Voltage 2 200 VAC 4 400 VAC 3 Rated Load Current 075 75 A 150 150 A 4 Terminal Type B Screw terminals 5 Zero Cross Function Blank Equipped with zero cross function Ordering Information List of Models The built in Thyristor Modules can be replaced Refer to the table on page 200 for the model number Note When ordering specify the rated input voltage 1 2 3 4 5 G3...

Страница 2: ...0 to 484 VAC G3NH 2150B 100 to 240 VAC 75 to 264 VAC 1 to 150 A 1 800 A 60 Hz 1 cycle G3NH 4150B 180 to 440 VAC 150 to 484 VAC Item G3NH 2075B G3NH 4075B G3NH 2150B G3NH 4150B Operate time 1 2 of load power source cycle 1 ms max DC input 3 2 of load power source cycle 1 ms max AC input Release time 1 2 of load power source cycle 1 ms max DC input 3 2 of load power source cycle 1 ms max AC input Ou...

Страница 3: ...0 20 30 0 20 30 50 37 25 60 0 G3NH 150B G3NH 075B Vertical mounting Horizontal mounting Vertical mounting Horizontal mounting Ambient temperature C Load current A Inrush current A Peak Energized time ms G3NH 75 to 264 VAC Input current mA Input voltage V Input current mA Input voltage V Input impedance kΩ G3NH 4 to 30 VDC Input current Impedance Input current Impedance Input impedance kΩ Name Appl...

Страница 4: ...p clean the jointing surfaces of the heat sink and thyristor module and apply the new grease supplied as an accessory to the jointing surfaces Secure the thyristor module to the heat sink with the two screws D and tighten each screw to a torque of 2 45 to 2 94 N m 7 Connect the thyristor module to the PWB with the socket The socket may be inserted in either direction Assemble the Base Assembly wit...

Страница 5: ...eat sink will rise by approximately 50 C with a rated current flow through the G3NH The G3NH will rise the ambient temperature When mounting the G3NH inside a panel install a fan for proper ventilation When closely mounting the G3NH Solid State Relays side by side reduce the load current 30 lower than the specified value shown in the load current vs ambient temperature graph Take proper measures s...

Отзывы: