E5L

5

Operating the E5L-C

@

Set temperature

1.

Press the 

 Key to enter the Set Temperature Mode.

2.

Press the 

 and 

 Keys to set the temperature. The display 

will continue to change for as long as the key is held down.

Note:

The default setting is the lowest temperature in the range.

Setting the Hysteresis

1.

Press the 

 Key to enter the Hysteresis Mode.

2.

Press the 

 and 

 Keys to set the value. Each time the key is 

pressed, the setting will change by 1

°

C. The setting will not 

continue to change even if the key is held down. The key must be 
released after each change. The hysteresis can be set from 1 to 
9

°

C, in increments of 1

°

C.

Note:

The default setting is 1

°

C.

Setting the Temperature Input Shift

1.

Press the 

 Key for at least 3 s to enter the Temperature Input 

Shift Mode.

2.

Press the 

 and 

 Keys to set the value. Each time the key is 

pressed, the setting will change by 1

°

C. The setting will not 

continue to change as the key is held down. The key must be 
released after each change. 
The input shift can be set from 

9 to 9

°

C, in increments of 1

°

C.

Note: 1.

The default setting is 0

°

C.

2.

The control output turns OFF while this setting is being 
made.

Setting Direct or Reverse Operation

1.

Press the 

 Key for at least 3 s to enter the Direct/Reverse 

Selection Mode.

2.

Press the 

 and 

 Keys to set the value. Direct operation can 

be set by pressing the 

 Key, and reverse operation can be set 

by pressing the 

 Key.

Note: 1.

The default setting is for reverse operation.

2.

The control output turns OFF while this setting is being 
made.

Process value

Power ON

Set temperature 
display

Process value 
display

Setting Protection

Press the       Key 
for at least 3 s.

Press the       Key 
for less than 1 s.

Temperature Input Shift

Direct/Reverse 

Operation

Set 
temperature

Hysteresis

Control stops.

Press the      
and      Keys 
for at least 1 s.

Press the      
and      Keys 
for at least 1 s.

Press the       and       Keys for at least 1 s.

Press the       Key for at least 3 s.

Press the       Key 
for at least 3 s.

Press the       Key 
for less than 1 s.

Press the       Key 
for less than 1 s.

Hysteresis

Display

+1

°

C

+5

°

C

+9

°

C

OFF

Power ON

Set temperature 

example: -5°C

4°C

OFF

Power ON

Hysteresis (1°C set)

Example: 

64°C

Set temperature: 

65°C

Control output (relay)

Control output (relay)

Hysteresis (1°C set)

Reverse Operation (Heating Control) Direct Operation (Cooling Control)

Input shift display

Thermistor measured 

temperature

Tempera-

ture dis-

play

(No shift)

25

°

C

25

°

C

(+9

°

C shift)

25

°

C

34

°

C

(-9

°

C shift)

25

°

C

16

°

C

Direct/reverse operation

Display

Reverse operation

Direct operation 

Содержание E5L-C Series

Страница 1: ...ic Thermostats E5L A E5L C Note The E5L C is not available with a set temperature range of 0 to 50 C Options Order Separately Sockets 1 2 E5L 1 Setting and Indication Methods A Analog setting no display C Digital setting display 2 Set temperature 30 20 30 to 20 C 0 50 0 to 50 C 0 100 0 to 100 C 100 200 100 to 200 C Size Type Control method Control output Model 45 35 mm Plug in ON OFF operation Rel...

Страница 2: ... 100 to 200 C models 10 C Influence of temperature 1 of PV or 2 C whichever is greater 1 digit max Influence of voltage Sampling period 2 s Insulation resistance 100 MΩ max at 500 VDC Dielectric strength 2 300 VAC 50 60 Hz for 1 min between charged terminals and uncharged metallic parts between power supply terminals and input terminals between power supply terminals and output terminals and betwe...

Страница 3: ...power supply 100 to 240 VAC Element interchangeable Thermistor 250 VAC 10 A Control output Input power supply 100 to 240 VAC Element interchangeable Thermistor Hysteresis adjuster DIFF Operation indicator Temperature dial Operation Indicator Operation indicator Output status Heating load Cooling load Lit red ON OFF Not lit OFF ON E5L A Mode Key Down Key Up Key Operation indicator Set value indicat...

Страница 4: ... 100 to 200 C Models Mounting Brackets Two 30 max 45 5 max 78 5 max Two 4 5 x 6 mounting holes 8 35 4 3 4 7 0 2 14 M3 5 x 8 Sems screws 7 0 2 33 max 45 5 max 78 5 max Two 4 5 x 6 mounting holes 14 M3 5 x 8 Sems screws 8 35 5 3 4 PTF14A PTF14A E Socket with Finger Protection 8 11 10 9 12 13 14 7 6 5 4 3 2 1 TOP VIEW 68 0 3 36 0 2 Two M4 or 4 5 dia holes TOP VIEW Note Can be mounted to a DIN Track C...

Страница 5: ...made Setting Direct or Reverse Operation 1 Press the Key for at least 3 s to enter the Direct Reverse Selection Mode 2 Press the and Keys to set the value Direct operation can be set by pressing the Key and reverse operation can be set by pressing the Key Note 1 The default setting is for reverse operation 2 The control output turns OFF while this setting is being made Process value Power ON Set t...

Страница 6: ...settings are being changed except for memory errors The control output status will be as shown in the above table while the set temperature or hysteresis is being set The control output will be OFF while the temperature input shift or direct reverse operation setting is being set Key operations will be possible when an error occurs except for a memory error 2 The setting protection indicator and s...

Страница 7: ... locations Locations directly subject to heat radiated from heating equipment Locations subject to water or oil Locations subject to direct sunlight Locations subject to dust or corrosive gas in particular sulfide gas and ammonia gas Locations subject to sudden or extreme temperature changes Locations subject to icing or condensation Locations subject to vibration or shock 2 Use and store the Prod...

Страница 8: ...is to extend the life of the relay by preventing relay chattering caused by the control output turning ON and OFF frequently Do not change the setting of the temperature dial more than 20 times Mounting the Thermistor Select a location for the temperature sensor of the thermistor where the temperature distribution of sensing objects will not be changed by installation Insert the temperature sensor...

Страница 9: ...9 MEMO ...

Страница 10: ...MEMO 10 ...

Страница 11: ...D INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards codes or regulations that apply to the combination of products in the customer s application or use of the products Take all necessary steps to determine the suitability of th...

Страница 12: ...mburg IL 60173 5302 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA CO LTD Room 2211 Bank of China Tower 200 Yin Cheng Zhong Road PuDong New Area Shanghai 200120 China Tel 86 21 5037 2222 Fax 86 21 5037 2200 Control Devices Division H Q Analog Controlle...

Отзывы: