 Inputting Parameters

The Temperature Controller has three display levels, 0, 1, and 2, in which only specific parameters can be set. Level 0 is the initial and is auto-
matically entered at power application. To change the mode to set or change a different group of parameters, hold down the Level Key for 2
seconds minimum. The display level mode changes as shown below. Actual displays vary with models and switch settings. If a display does not
appear as expected, check your switch settings.

–––––––

–––––––

–––––––

Level 0

Power ON

Level 1

Level 2

Press the Level Key.

Press the Level Key.

Press the Level Key.

Valve travel, main set-
ting, alarm set value,
input shift, PID con-
stants

Lower/upper setting limit,
alarm hysteresis, disable
band, motor calibration, Fully
open/close position, Opening/
closing time

Input type, alarm mode

Level 0

Process value

m    0

Process value

0

Press 

a

.

a    0

al

0

in-5

0

p

40.0

i

240

d

40

Press 

a

.

Press 

a

.

Press 

a

.

Press 

a

.

Press 

a

.

Press 

a

.

Press 

a

.

Valve travel

Main setting

Valve travel

Alarm value

Input shift

Proportional band

Integral time

Derivative time

(Note 1)

(Note 2)

(Note 3)

(Note 4)

(Note 5)

(Note 5)

(Note 5)

Process value

PV

SV

Note:

1. Not displayed in automatic output mode. “

m--- 

” will be

displayed if a potentiometer is not connected.

2. Not displayed in manual output mode. “

a--- 

” will be dis-

played if a potentiometer is not connected.

3. Not displayed when the alarm is disabled (SW203 set to

0 or 9).

4. Not displayed when the input shift display is disabled

(SW201, pin 3 OFF).

5. Not displayed when PID display is disabled (SW201, pin

6 OFF).

Main Setting

The set point can be changed with the Up and Down Keys.

Valve Travel

The value travel can be monitored. If a potentiometer is not con-
nected, the display will show “

a--- 

” for automatic and ”

m--- 

” for

manual operation. While “

m--- 

” is displayed in manual output

mode, the Up Key will turn ON the OPEN output and the Down Key
will turn ON the CLOSE output.

Selecting the Output Mode

The A/M Key can be pressed for one second or longer to change
between the automatic and manual output modes. The balance-
less-bumpless function will operate to prevent the output from
changing abruptly.

Automatic Output Mode

In automatic output mode, the control will function automatically.
When the A/M Key is pressed and the automatic output mode is first
entered, displays like the following will appear (display level 0).

123

80

PV

SV

Process value

Main setting

Manual Output Mode

In manual output mode, the controller  can be operated with the Up
and Down Keys. The Up Key will turn the OPEN output ON and light
the OPEN indicator. The Down Key will turn ON the CLOSE output
and light the CLOSE indicator. 
When the A/M Key is pressed and the manual output mode is first
entered, displays like the following will appear (display level 0).

123

m 80

PV

SV

Process value

Valve position (%)

Содержание E5EX-P

Страница 1: ...Temperature Ranges Input switch selectable Thermocouple Temperature resistance thermometer K Chromel vs alumel J L Iron vs constantan T U Copper vs constantan E Chromel vs constantan R Platinum vs platinum 13 rhodium S Platinum vs platinum 10 rhodium PT platinum resistance thermometer Pt100 JPt100 Range C 200 to 1 300 100 to 850 200 to 400 0 to 600 0 to 1 700 0 to 1 700 99 9 to 450 0 F 300 to 2 30...

Страница 2: ... 250 VAC resistive load inrush current 1 A max Control mode PID control with auto tuning Alarm output Relay output SPST NO contacts 3 A 250 VAC resistive load Setting method Digital setting via Up and Down Keys Indication method Digital indications character heights PV 11 mm and SV 8 mm Color PV red SV green Other functions Upper and lower limits for set value Key protection Input shift Display un...

Страница 3: ... in units of 1 C F Platinum resistance thermometer 99 9 to 999 9 C F in units of 0 1 C F Insulation resistance 20 MΩ min at 500 VDC Dielectric strength 2 000 VAC 50 60 Hz for 1 min between terminals of different polarities Vibration resistance Malfunction 2 to 55 Hz 2G 10 min each in X Y and Z directions Destruction 10 to 55 Hz 0 75 mm double amplitude 2 hrs each in X Y and Z directions Shock resi...

Страница 4: ...hange levels to set different groups of pa rameters Open Output Indicator Lights when the open out put is ON Manual Output Mode In dicator Lights when in manual mode Close Output Indicator Lights when the close out put is ON Operation NOTICE Always turn off the power supply to the Electronic Temperature Controller before changing any switch settings Settings 1 Remove the internal mechanism from th...

Страница 5: ... 0 to 1 100 6 JPt100 99 9 to 450 0 99 9 to 800 0 7 Pt100 99 9 to 450 0 99 9 to 800 0 8 L 100 to 850 100 to 1 500 9 U 200 to 400 300 to 700 Operating Mode Selector SW201 FUNCTION This DIP switch selects the operation modes listed in the following table Function Pin number Pin setting Control setting Not used 1 Leave turned OFF Control output 2 ON Normal cooling OFF Reverse heating Input shift 3 ON ...

Страница 6: ...tance thermome ter 99 9 to 999 9 C F 4 Upper and lower limit range alarm X X Thermocouple 0 to 9 999 C F 5 Upper and lower limit alarm with standby se quence 3 e X X Platinum resistance thermometer 0 to 999 9 C F 6 Upper limit alarm with standby sequence e X X Thermocouple 999 to 9 999 C F 7 Lower limit alarm with standby sequence 3 X X Platinum resistance thermome ter 99 9 to 999 9 C F 8 Absolute...

Страница 7: ...en press the Display Key until calb is displayed This is the initial mode when power is turned on for the first time 2 Simultaneously press the Up and Down Keys for at least one second fr h will be displayed the OPEN output will turn ON and the valve will start to open Press the Display Key as soon as the valve stops by the limit switch built into the motor The count value for the fully open posit...

Страница 8: ...layed if a potentiometer is not connected 3 Not displayed when the alarm is disabled SW203 set to 0 or 9 4 Not displayed when the input shift display is disabled SW201 pin 3 OFF 5 Not displayed when PID display is disabled SW201 pin 6 OFF Main Setting The set point can be changed with the Up and Down Keys Valve Travel The value travel can be monitored If a potentiometer is not con nected the displ...

Страница 9: ...the propor tional band P constant can be changed using the Up and Down Keys The new value will be displayed on the SV display It can be set in a range from 0 1 to 999 9 C F in units of 0 1 C F The facto ry setting is 40 0 C F NOTICE The output value will change according to the differ ence between the set value and the present value when the proportional band is changed during control operation If...

Страница 10: ...ibrate the motor during control operation Make sure that control operations have been stopped before calibrating fr h Fully open position fr l Fully closed position mot Opening closing time The motor is calibrated Refer to page 9 Level 2 In level 2 selected input sensor and modes for alarm output can be monitored Note that level 2 is a monitoring level only and thus no parameters can be changed Wh...

Страница 11: ... down the Level Key and Mode Key again simultaneously for 1 second minimum All settings will re turn to those prior to the beginning of auto tuning Automatic tuning can be executed at any time at power application while the temper ature is rising or after the control action has stabilized Error Messages The Temperature Controller is provided with self diagnostic functions and will display an error...

Страница 12: ...e 1 Connect a valve position indicator if required 2 Do not connect unused terminals Control output Open Close Alarm output Potentiometer input see Note 1 100 to 240 VAC 50 60 Hz Ground FG terminal 17 under noise interfered environment Use these terminals when connecting a platinum resistance thermometer remove short bar from terminals 13 and 14 Use these terminals when connecting a thermo couple ...

Страница 13: ...ay damage them The terminal block of the Temperature Controller is constructed so that the lead wires can be connected to all the terminals from the same direction Top Bottom Input Connection To reduce inductive noise influence the lead wires connecting the input to the Temperature Controller must be separated from the power lines and load lines Use the specified compensating conductors for thermo...

Страница 14: ...saka 540 Japan Phone 06 949 6070 Fax 06 949 6084 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H55 E1 1 In the interest of product improvement specifications are subject to change without notice Printed in Japan 0691 1M ...

Отзывы: