background image

E5CD-800/E5ED-800

41

Service Life

1.

Use the Digital Temperature Controller within the following 

temperature and humidity ranges:

Temperature: 

10 to 55°C (with no icing or condensation), 

Humidity: 25% to 85%

If the Digital Temperature Controller is installed inside a control 

board, the ambient temperature must be kept to under 55°C, 

including the temperature around the Digital Temperature 

Controller.

2.

The service life of electronic devices like Digital Temperature 
Controllers is determined not only by the number of times the relay 
is switched but also by the service life of internal electronic 
components. Component service life is affected by the ambient 
temperature: the higher the temperature, the shorter the service 
life and, the lower the temperature, the longer the service life. 
Therefore, the service life can be extended by lowering the 
temperature of the Digital Temperature Controller.

3.

When two or more Digital Temperature Controllers are mounted 
horizontally close to each other or vertically next to one another, 
the internal temperature will increase due to heat radiated by the 
Digital Temperature Controllers and the service life will decrease. 
In such a case, use forced cooling by fans or other means of air 
ventilation to cool down the Digital Temperature Controllers. When 
providing forced cooling, however, be careful not to cool down the 
terminals sections alone to avoid measurement errors.

Ensuring Measurement Accuracy

1.

When extending or connecting the thermocouple lead wire, be 

sure to use compensating wires that match the thermocouple 

types.

2.

When extending or connecting the lead wire of the platinum 
resistance thermometer, be sure to use wires that have low 
resistance and keep the resistance of the three lead wires the 
same.

3.

Mount the Digital Temperature Controller so that it is horizontally 
level.

4.

If the measurement accuracy is low, check to see if input shift has 
been set correctly.

Resistance to Water

The degree of protection is as shown below. Sections without any 
specification on their degree of protection or those with IP

0 are not 

waterproof.
Front panel: IP66
Rear case: IP20, Terminal section: IP00
When waterproofing is required, insert the Waterproof Packing on the 
backside of the front panel.
Keep the Port Cover on the front-panel Setup Tool port of the E5ED-
800 securely closed. The degree of protection when the Waterproof 
Packing is used is IP66. To maintain an IP66 degree of protection, the 
Waterproof Packing and the Port Cover for the front-panel Setup Tool 
port must be periodically replaced because they may deteriorate, 
shrink, or harden depending on the operating environment.
The replacement period will vary with the operating environment. 
Check the required period in the actual application. Use 3 years or 
sooner as a guideline. If the Waterproof Packing and Port Cover are 
not periodically replaced, waterproof performance may not be 
maintained.
If a waterproof structure is not required, then the Waterproof Packing 
does not need to be installed.

Precautions during Operation

1.

It takes approximately two seconds for the outputs to turn ON from 

after the power supply is turned ON. Design the system (e.g., 

control panel) to allow for this delay.

2.

Make sure that the Digital Temperature Controller has 30 minutes 
or more to warm up after turning ON the power before starting 
actual control operations to ensure the correct temperature 
display.

3.

Avoid using the Digital Temperature Controller in places near a 
radio, television set, or wireless installing. The Digital Temperature 
Controller may cause radio disturbance for these devices.

Mounting

E5CD-800

Mounting to the Panel

1.

For waterproof mounting, waterproof packing must be installed on 

the Digital Temperature Controller. Waterproofing is not possible 

when group mounting several Digital Temperature Controllers.

2.

Insert the E5CD-800 into the mounting hole in the panel.

3.

Push the Adapter from the terminals up to the panel, and 
temporarily fasten the E5CD-800.

4.

Tighten the two fastening screws on the Adapter. Alternately 
tighten the two screws little by little to maintain a balance. Tighten 
the screws to a torque of 0.29 to 0.39 N·m.

Mounting the Terminal Cover

There are two models of Terminal Covers that you can use with the 
E5CD-800.
Slightly bend the E53-COV23 Terminal Cover to attach it to the 
terminal block as shown in the following diagram. The Terminal Cover 
cannot be attached in the opposite direction. Or, you can use the E53-
COV17 Terminal Cover. Make sure that the “UP” mark is facing up, 
and then attach the E53-COV17 Terminal Cover to the holes on the 
top and bottom of the Digital Temperature Controller.

E5ED-800

Precautions for Correct Use

Adapter

Waterproof packing 

Panel

E53-COV17
Terminal Cover 
(Sold separately.)

Adapter

E53-COV23
Terminal Cover
(Sold Separately)

Fastening 
screws

Terminal Cover
(E53-COV17) 
(Sold separately.)

Adapter

• E53-COV17

• E53-COV23

Enlarged Illustration of 
Terminal Section

Slightly bend 
the E53-COV23 
Terminal Cover 
in the direction 
shown by the 
arrows to attach 
it to the terminal 
block.

Adapter

Waterproof packing 

Panel

E53-COV24
Terminal Cover 
(Sold Separately)

Adapter

E53-COV24
Terminal Cover 
(Sold Separately)

Fastening screws

Содержание E5CD-800

Страница 1: ...CD 800 E5ED 800 Temperature Sensors E52 Accurately Measure Seal Temperatures Temperature Sensors for Packaging Machines Next Generation Digital Temperature Controllers E5CD 800 48 48 mm and E5ED 800 48 96 mm Optimize Control by Detecting Status Changes Easily Satisfy Both Productivity and Quality ...

Страница 2: ...ty standards refer to your OMRON website Auxiliary Outputs 2 independent outputs Bar displays E5CD 800 Adaptive Control Automatic Filter Adjustment Water cooling Output Adjustment Indication Data Power ON Time Ambient Temperature Output ON OFF Count Sensor Input Dual displays PV SV 4 digit displays Universal input Thermocouple Pt Analog current voltage Indication Accuracy Thermocouple input 0 3 PV...

Страница 3: ...different heating and cooling response characteristics List of Models Model A B C D E F Meaning Control outputs 1 and 2 No of auxiliary outputs Power supply voltage Terminal type Input type Options E5CD 48 48 mm Control output 1 Control output 2 RX Relay output None QX Voltage output for driving SSR None 2 2 independent outputs A 100 to 240 VAC D 24 VAC DC D Screw terminal blocks draw out structur...

Страница 4: ... use these CTs Adapter Note Use this Adapter when the panel has already been prepared for an E5B Controller Waterproof Cover Mounting Adapter Note This Mounting Adapter is provided with the Digital Temperature Controller DIN Track Mounting Adapter Front Covers Draw out Jig Model E53 COV17 E53 COV23 3pcs Model Y92S P8 Hole diameter Model 5 8 mm E54 CT1 5 8 mm E54 CT1L 12 0 mm E54 CT3 12 0 mm E54 CT...

Страница 5: ...d Electrical life 100 000 operations Minimum applicable load 10 mA at 5 V reference values Setting method Digital setting using front panel keys Indication method 11 segment digital display individual indicators and bar display Character height PV 14 9 mm SV 7 1 mm Multi SP Up to eight set points SP0 to SP7 can be saved and selected using the key operations or serial communications Bank switching ...

Страница 6: ...erature sensor Sensor specification Pt100 JPt100 K J T E L U N R S B C W PLII 10 to 70 C 60 to 120 C 115 to 165 C 140 to 260 C 2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 100 200 2300 1800 1700 1700 1300 1300 1300 850 850 850 600 500 0 500 0 500 0 400 0 400 400 0 400 400 0 260 120 165 100 0 100 0 90 0 0 0 0 0 0 0 0 0 0 0 0 0 20 0 100 20 0 100 200 199 9 1...

Страница 7: ...y sequence A standby sequence is added to the lower limit alarm 3 6 8 Absolute value upper limit The alarm will turn ON if the process value is larger than the alarm value X regardless of the set point 9 Absolute value lower limit The alarm will turn ON if the process value is smaller than the alarm value X regardless of the set point 10 Absolute value upper limit with standby sequence A standby s...

Страница 8: ...emperature Controllers User s Manual Cat No H224 for information on the operation of the standby sequence 7 Refer to the E5 D Digital Temperature Controllers User s Manual Cat No H224 for information on the loop burnout alarm LBA 8 Refer to the E5 D Digital Temperature Controllers User s Manual Cat No H224 for information on the PV change rate alarm 9 When heating cooling control is performed the ...

Страница 9: ...to 9999 s in units of 1 s 0 0 to 999 9 s in units of 0 1 s 4 Disturbance derivative time 0 to 9999 s in units of 1 s 0 0 to 999 9 s in units of 0 1 s 4 Control period 0 1 0 2 0 5 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in units of 0 1 Alarm setting range 1999 to 9999 decimal point position depends on input type Influence of signal source resistance Thermocouple 0 1 C Ω max 100 Ω ...

Страница 10: ...tic Field Strength EN 55011 Group 1 class A Noise Terminal Voltage EN 55011 Group 1 class A EMS EN 61326 1 5 ESD Immunity EN 61000 4 2 Electromagnetic Field Immunity EN 61000 4 3 Burst Noise Immunity EN 61000 4 4 Conducted Disturbance Immunity EN 61000 4 6 Surge Immunity EN 61000 4 5 Voltage Dip Interrupting Immunity EN 61000 4 11 ...

Страница 11: ... with CompoWay F or CRC 16 Modbus Flow control None Interface RS 485 Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default 20 ms Programless communications You can use the memory in the PLC to read and write E5CD 800 parameters start and stop operation etc The E5CD 800 automatically performs communications with PLCs No communications programming i...

Страница 12: ...85 17 18 12 15 16 1 2 13 14 3 11 4 6 7 8 9 10 5 The E5CD 800 is set for a K type thermocouple input type 5 by default An input error s err will occur if the input type setting does not agree with the temperature sensor Check the input type Relay output 250 VAC 3 A resistive load Voltage output for driving SSR 12 VDC 21 mA Relay outputs 250 VAC 3 A resistive load no polarity 100 to 240 VAC 24 VAC D...

Страница 13: ... 1 0 0 Panel Cutout Mounted Separately Group Mounted Mounting Adapter Accessory Waterproof Packing Accessory 44 8 44 8 4 1 60 64 58 48 48 E5CD 800 Recommended panel thickness is 1 to 5 mm Group mounting is not possible in the vertical direction Main tain the specified mounting space between Controllers To mount the Controller so that it is waterproof insert the water proof packing onto the Control...

Страница 14: ...terproof Packing separately if it becomes lost or damaged The Waterproof Packing can be used to achieve an IP66 degree of protection Deterioration shrinking or hardening of the waterproof packing may occur depending on the operating environment Therefore periodic replacement is recommended to ensure the level of waterproofing specified in IP66 The time for periodic replacement depends on the opera...

Страница 15: ...aximum continuous heater current 50 A 50 60 Hz Number of windings 400 2 Winding resistance 18 2 Ω Thru current Io A r m s 1 10 100mA 1 10 100 1 000A 100V Frequency 50 Hz Distortion factor 10 3 1 100Ω RL 10Ω 10 1 100mV 10 1 100μV 10 1kΩ Output voltage Eo V r m s E54 CT1L 5 8 dia Filler epoxy Case PBT Shrinkable tube Two 3 5 dia Cable AWG18 25 2 5 115 5 8 21 10 5 40 30 5 15 10 Mark yellow 12 ...

Страница 16: ...or E54 CT3L Maximum continuous heater current 120 A 50 60 Hz Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A Number of windings 400 2 Winding resistance 8 0 8 Ω Thru current Io A r m s 1 10 100mA 1 10 100 1 000A 100V Frequency 50 Hz Distortion factor 10 3 1 1kΩ 100Ω 50Ω RL 10Ω 500Ω 10 1 100mV 10 1 100μV 10 Output voltage Eo V r m s Filler epoxy Case PBT Cable ...

Страница 17: ...ready been prepared for the E5B 2 Only black is available 3 You cannot use it together with the Y92F 49 Adapter that is enclosed with the Controller 50 61 3 5 38 48 80 5 Y92F 52 Mounting Example Note This Adapter cannot be used together with the Terminal Cover Remove the Terminal Cover to use the Adapter This Adapter is used to mount the E5CD 800 to a DIN Track If you use the Adapter there is no n...

Страница 18: ... is provided with the Digital Temperature Controller Order this Adapter separately if it becomes lost or damaged This Front Cover is soft type It is able to operate the controller with using this cover This Front Cover is hard type Please use it for the mis operation prevention etc 55 5 43 6 35 2 Use this Draw out Jig to remove the interior body of the Digital Temperature Controller from the case ...

Страница 19: ...MEMO 19 ...

Страница 20: ...ite Dual displays PV SV 1 E5ED 800 Auxiliary Outputs 2 Bar displays 2 Adaptive Control Automatic Filter Adjustment Water cooling Output Adjustment Indication Data Power ON Time Ambient Temperature Output ON OFF Count Sensor Input 4 digit displays Universal input Thermocouple Pt Analog current voltage Indication Accuracy Thermocouple input 0 3 PV Pt input 0 2 of PV Analog input 0 2 of FS Sampling P...

Страница 21: ... provided with the Digital Temperature Controller Current Transformers CTs Lead wires are included with these CTs If UL certification is required use these CTs Draw out Jig Model A B C D E F Meaning Control outputs 1 and 2 No of auxiliary outputs Power supply voltage Terminal type Input type Options E5ED 48 96 mm Control output 1 Control output 2 RX Relay output None QX Voltage output for driving ...

Страница 22: ...0 kΩ min Non contact input ON Residual voltage 1 5 V max OFF Leakage current 0 1 mA max Current flow Approx 7 mA per contact Setting method Digital setting using front panel keys Indication method 11 segment digital display individual indicators and bar display Character height PV 18 0 mm SV 11 0 mm MV 7 8 mm Three displays Contents PV SV MV PV SV Multi SP PV SV Remaining soak time etc Numbers of ...

Страница 23: ...erature sensor Sensor specification Pt100 JPt100 K J T E L U N R S B C W PLII 10 to 70 C 60 to 120 C 115 to 165 C 140 to 260 C 2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 100 200 2300 1800 1700 1700 1300 1300 1300 850 850 850 600 500 0 500 0 500 0 400 0 400 400 0 400 400 0 260 120 165 100 0 100 0 90 0 0 0 0 0 0 0 0 0 0 0 0 0 20 0 100 20 0 100 200 199 9 1...

Страница 24: ...by sequence A standby sequence is added to the lower limit alarm 3 6 8 Absolute value upper limit The alarm will turn ON if the process value is larger than the alarm value X regardless of the set point 9 Absolute value lower limit The alarm will turn ON if the process value is smaller than the alarm value X regardless of the set point 10 Absolute value upper limit with standby sequence A standby ...

Страница 25: ...emperature Controllers User s Manual Cat No H224 for information on the operation of the standby sequence 7 Refer to the E5 D Digital Temperature Controllers User s Manual Cat No H224 for information on the loop burnout alarm LBA 8 Refer to the E5 D Digital Temperature Controllers User s Manual Cat No H224 for information on the PV change rate alarm 9 When heating cooling control is performed the ...

Страница 26: ...to 9999 s in units of 1 s 0 0 to 999 9 s in units of 0 1 s 4 Disturbance derivative time 0 to 9999 s in units of 1 s 0 0 to 999 9 s in units of 0 1 s 4 Control period 0 1 0 2 0 5 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in units of 0 1 Alarm setting range 1999 to 9999 decimal point position depends on input type Influence of signal source resistance Thermocouple 0 1 C Ω max 100 Ω ...

Страница 27: ...tic Field Strength EN 55011 Group 1 class A Noise Terminal Voltage EN 55011 Group 1 class A EMS EN 61326 1 5 ESD Immunity EN 61000 4 2 Electromagnetic Field Immunity EN 61000 4 3 Burst Noise Immunity EN 61000 4 4 Conducted Disturbance Immunity EN 61000 4 6 Surge Immunity EN 61000 4 5 Voltage Dip Interrupting Immunity EN 61000 4 11 ...

Страница 28: ... with CompoWay F or CRC 16 Modbus Flow control None Interface RS 485 Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default 20 ms Programless communications You can use the memory in the PLC to read and write E5ED 800 parameters start and stop operation etc The E5ED 800 automatically performs communications with PLCs No communications programming i...

Страница 29: ...23 22 23 24 Pt I 24 22 23 24 1 Control output 3 4 5 6 3 4 5 6 RX R Q OUT1 OUT1 A B B QX 21 19 20 17 18 15 16 808 Communications 2 event inputs and 1 CT input 13 14 EV1 EV2 B A RS 485 CT1 2 Auxiliary Outputs 7 8 11 12 Auxiliary outputs 1 2 9 10 Auxiliary output 1 The E5ED 800 is set for a K type thermocouple input type 5 by default An input error s err will occur if the input type setting does not ...

Страница 30: ...eter Bar display E5ED 800 45 0 6 0 92 0 8 0 120 min 48 number of units 2 5 1 0 0 Mounted Separately Group Mounted 92 0 8 0 Group mounting does not allow waterproofing Mounting Adapter Accessory Waterproof Packing Accessory 96 110 48 60 64 4 44 91 1 E5ED 800 Recommended panel thickness is 1 to 8 mm Group mounting is not possible in the vertical direction Maintain the specified mounting space betwee...

Страница 31: ...66 degree of protection Deterioration shrinking or hardening of the waterproof packing may occur depending on the operating environment Therefore periodic replacement is recommended to ensure the level of waterproofing specified in IP66 The time for periodic replacement depends on the operating environment Be sure to confirm this point at your site Consider three years as a rough standard Mounting...

Страница 32: ... 7 67 6 28 9 21 9 2 Waterproof Cover Y92A 49N for DIN 48 96 103 4 53 6 35 2 Use this Draw out Jig to remove the interior body of the Digital Temperature Controller from the case to perform maintenance without removing the terminal wiring ...

Страница 33: ...aximum continuous heater current 50 A 50 60 Hz Number of windings 400 2 Winding resistance 18 2 Ω Thru current Io A r m s 1 10 100mA 1 10 100 1 000A 100V Frequency 50 Hz Distortion factor 10 3 1 100Ω RL 10Ω 10 1 100mV 10 1 100μV 10 1kΩ Output voltage Eo V r m s E54 CT1L 5 8 dia Filler epoxy Case PBT Shrinkable tube Two 3 5 dia Cable AWG18 25 2 5 115 5 8 21 10 5 40 30 5 15 10 Mark yellow 12 ...

Страница 34: ...or E54 CT3L Maximum continuous heater current 120 A 50 60 Hz Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A Number of windings 400 2 Winding resistance 8 0 8 Ω Thru current Io A r m s 1 10 100mA 1 10 100 1 000A 100V Frequency 50 Hz Distortion factor 10 3 1 1kΩ 100Ω 50Ω RL 10Ω 500Ω 10 1 100mV 10 1 100μV 10 Output voltage Eo V r m s Filler epoxy Case PBT Cable ...

Страница 35: ...the S Key 3 Protect Level Calibration Level Manual Control Level Press the O Key for at least 1 s Press the O Key for at least 1 s or the S Key for at least 1 s 1 Used to set the MV manually Used for SP alarm values and other basic settings and monitoring Used to set protection for operations Used to change adjustment parameters PID constants adjustment sensitivity etc Press the O M Keys for at le...

Страница 36: ...power or after a software reset Used with programless communications Power ON Adjustment Level Press the O Key less than 1 s Manual Control Level Adjustment Level Display Displayed only once when entering adjustment level AT Execute Cancel Communications Writing Heater Current 1 Value Monitor Heater Burnout Detection 1 Leakage Current 1 Monitor HS Alarm 1 SP 4 SP 5 SP 6 SP 7 SP 0 SP 1 SP 2 SP 3 Pr...

Страница 37: ...ing password 169 Parameter Initialization Number of Multi SP Points SP Ramp Time Unit Standby Sequence Reset Auxiliary Output 1 Open in Alarm Auxiliary Output 2 Open in Alarm Auxiliary Output 3 Open in Alarm HB ON OFF Heater Burnout Latch Heater Burnout Hysteresis AT Calculated Gain α AT Hysteresis Limit Cycle MV Amplitude Automatic Display Return Time Alarm 1 Latch Alarm 2 Latch Alarm 3 Latch Mov...

Страница 38: ...en on the left the number without the decimal point Control continues and operation is normal The value will appear in the display for the PV Refer to the E5 D Digital Temperature Controllers User s Manual Cat No H224 for information on the controllable range Above 9 999 e333 A D converter error There is an error in the internal circuits After checking the input error turn the power OFF then back ...

Страница 39: ...l operations impossible or prevent alarm outputs resulting in property damage To maintain safety in the event of malfunction of the Digital Temperature Controller take appropriate safety measures such as installing a monitoring device on a separate line CAUTION Risk of Fire and Electric Shock a This product is UL listed as Open Type Process Control Equipment It must be mounted in an enclosure that...

Страница 40: ...e load e g heater at the same time as or before supplying power to the Digital Temperature Controller If power is turned ON for the Digital Temperature Controller before turning ON power for the load tuning will not be performed properly and optimum control will not be achieved 12 During tuning ensure that the power for the load e g heater is ON If the power supply to the load e g heater is not tu...

Страница 41: ...ront panel Setup Tool port must be periodically replaced because they may deteriorate shrink or harden depending on the operating environment The replacement period will vary with the operating environment Check the required period in the actual application Use 3 years or sooner as a guideline If the Waterproof Packing and Port Cover are not periodically replaced waterproof performance may not be ...

Страница 42: ...ly pull out the Digital Temperature Controller laterally If you pull the interior body out at an angle the Digital Temperature Controller may be damaged 4 After the interior body is free from the rear case support the interior body with one hand and pull it out slowly in a horizontal direction 2 Prepare the new interior body 1 Place the Digital Temperature Controller flat on a table and slowly ins...

Страница 43: ...CD 800 or E5ED 800 use the following types of crimp terminals for M3 screws Although you can connect two crimp terminals with insulation sleeves to one terminal you cannot do so if the diameter of the insulation sleeves is too large Three year Guarantee Period of Guarantee The guarantee period of the Unit is three years starting from the date the Unit is shipped from the factory Scope of Guarantee...

Страница 44: ...age together with the automatic filter adjustment function of E5 D 800 Digital Temperature Controllers is recommended Temperature Sensors for Packaging Machines Refer to Safety Precautions for the E5CD 800 E5ED 800 Digital Temperature Controllers on page 39 Classification Description Model and appearance Temperature range Element type Conductor type Class Protective tubing material Terminal type S...

Страница 45: ... bending radius 2 mm Bendable section 8 mm or farther from the end Special models for Packaging Machines E 52 C A A Y D 1 S M Code Element type CA K Diameter D Length L 1 0 6 1 0 12 1 0 3 to 100 in centimeters variable Code Terminal type A Exposed lead wires Code Terminal processing Y Y type crimp terminals for M3 0 Code Lead wire length M m Specify the M length in meters Range 0 5 1 2 or 0 5 to 1...

Страница 46: ...ive tubing length L cm Lead wire type Lead wire length M m 0 5 1 2 Model Exposed lead Models 1 dia 6 Heat resistive E52 CA6AY D 1 S1 0 5M E52 CA6AY D 1 S1 1M Flexible Heat resistive E52 CA6AY D 1 S2 1M E52 CA6AY D 1 S2 2M 12 Heat resistive E52 CA12AY D 1 S1 0 5M E52 CA12AY D 1 S1 1M Flexible Heat resistive E52 CA12AY D 1 S2 1M E52 CA12AY D 1 S2 2M ...

Страница 47: ...ve bracket S2 Misumi Corporation Cable Clips COPU4 20P Digi Key Cable Clamp RPC1474 ND To correctly measure the surface temperature the following installation conditions are recommended Enlargement Bend to a radius of 2 mm or larger Insert the end by 8 mm or longer Approx 1 to 3 5 mm Heater Example 2 Groove for Temperature Sensor created in heating plate and Temperature Sensor secured with a cover...

Страница 48: ...MEMO 48 ...

Страница 49: ... CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity with any standards codes or regulations which apply to the combination of the Product i...

Страница 50: ...RON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA CO LTD Room 2211 Bank of China Tower 200 Yin Cheng Zhong Road PuDong New Area Shanghai 200120 China Tel 86 21 ...

Отзывы: