CHAPTER 2 CompoWay/F COMMUNICATIONS PROCEDURES
E5AN/EN/CN/GN
2--10
At occurrence of error
Response code
Error name
Cause
1002
Command too short
The command is too short.
1101
Area type error
Wrong variable type
1103
Start address out-of-
range error
Write start address is out of range.
1104
End address out-of-
range error
The write end address (write start
a number of elements)
exceeds the final address of the vari-
able area.
1003
Number of elements/
data mismatch
The number of data does not match
the number of elements.
1100
Parameter error
·
Bit position is other than “00”.
·
Write data is out of setting range.
3003
Read-only data
Variable type “C0” was written to.
2203
Operation error
·
The
“communications
writing”
parameter is set to “OFF” (dis-
abled).
·
Writing was carried out on the
parameters from setup areas 0 to 1.
·
Writing was carried out on a pro-
tected parameter other than in the
protect level.
·
Writing was carried out during AT
execution.
·
EEPROM error
* For details on AT (auto-tuning), refer to the separate User’s Manuals.
(5) Precautions
F
Alarm function
Even though alarms are not displayed on the controller’s display, they
are all functional in communications.