![Omron E5AN Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/omron/e5an/e5an_user-manual_742571012.webp)
CHAPTER 1 ABOUT COMMUNICATIONS METHODS
E5AN/EN/CN/GN
1--4
Match the communications specifications of the E5AN/EN/CN/GN and
the host computer. If a one-to-N system is being used, be sure that the com-
munications specifications of all devices in the system (except individual
unit numbers) are the same.
This section explains how to set the E5AN/EN/CN/GN’s communications
specifications. For details on the host computer, refer to the User’s Manual
provided with the host computer.
RS- -232C (Applies to the E5AN/EN only.)
·
RS- -232C connections are 1 : 1.
·
The total cable length is 15m max.
·
Use a shielded, twisted- -pair cable AWG28 or larger.
Host computer
RS232C : 25P
E5AN/EN
Cable reference diagram
E5GN
AWG24 to AWG14
Conductor cross--section
0.2047mm
2
to 2.081mm
2
E5AN/EN/CN
AWG28 or larger
Conductor cross--section
0.08042mm
2
or larger