3 Communications Data for CompoWay/F
3 - 18
E5@C Digital Temperature Controllers Communications Manual (H175)
C3 (83)
0073
PV/SP No. 1 Display
Selection
H'00000000 (0): Nothing displayed.
H'00000001 (1): PV/SP
H'00000002 (2): PV
H'00000003 (3): PV/SP (character display)
H'00000004 (4): PV/SP/MV
H'00000005 (5): PV/SP/Multi-SP No.
H'00000006 (6): PV/SP/Soak time remain
H'00000007 (7): PV/SP/Internal SP (ramp SP)
H'00000008 (8): PV/SP/Alarm value 1
Advanced
function
setting
C3 (83)
0074
MV Display Selection H'00000000 (0): MV (heating)
H'00000001 (1): MV (cooling)
C3 (83)
0075
PV Decimal Point
Display
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0076
PV Status Display
Function
H'00000000 (0): OFF
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
H'00000009 (9): Status display message
*1
C3 (83)
0077
SV Status Display
Function
H'00000000 to H'00000009 (0 to 9)
Note: Same as for PV Status Display
Function
C3 (83)
0083
Display Refresh
Period
H'00000000 (0): OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
C3 (83)
0084
Alarm 4 Type
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type.
However, the LBA (loop burnout alarm)
cannot be set.
Initial setting
C3 (83)
0085
Event Input
Assignment 5
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
C3 (83)
0086
Event Input
Assignment 6
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
C3 (83)
0087
Auxiliary Output 4
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function setting
C3 (83)
0088
Alarm 4 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
C3 (83)
0089
Moving Average
Count
H'00000000 (0): OFF
H'00000001 (1): 2 times
H'00000002 (2): 4 times
H'00000003 (3): 8 times
H'00000004 (4): 16 times
H'00000005 (5): 32 times
Advanced
function setting
C3 (83)
008A
Alarm 4 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
008B
Alarm 4 ON delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
008C
Alarm 4 OFF delay
H'00000000 to H'000003E7 (0 to 999)
*1
Selection is possible only with the E5DC and E5GC. (The D5DC must be manufactured in July 2014 or later
(version 2.2 or higher).)
Variable
type
Address
Parameter name
Setting (monitor) value
Level
Содержание E5AC
Страница 2: ......
Страница 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 54: ...2 CompoWay F Communications Procedures 2 22 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 96: ...4 Modbus Communications Procedure 4 16 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 114: ...5 Communications Data for Modbus 5 18 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 206: ...6 Programless Communications 6 92 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Страница 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 223: ......