5 - 13
5 Communications Data for Modbus
E5@C Digital Temperature Controllers Communications Manual (H175)
5-
1 Variab
le Area (Set
tin
g
Ran
g
e)
List
5
*1
Selection is possible only with the E5DC and E5GC. (The D5DC must be manufactured in July 2014 or later (version 2.2
or higher).)
*2
You can use this parameter only with the E5EC-PR
@
-8
@@
or E5AC-PR
@
-8
@@
. (The Digital Controller must be
manufactured in August 2014 or later (version 2.2 or higher).)
0F1C
2F0E
Auxiliary Output 2 Open
in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function
setting
0F1E
2F0F
Auxiliary Output 3 Open
in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
0F20
2F10
Auxiliary Output 4 Open
in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
0F22
2F11
Alarm 1 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F24
2F12
Alarm 2 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F26
2F13
Alarm 3 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F28
2F14
Alarm 4 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F2A
2F15
Alarm 1 OFF delay
H'00000000 to H'000003E7 (0 to 999)
0F2C
2F16
Alarm 2 OFF delay
H'00000000 to H'000003E7 (0 to 999)
0F2E
2F17
Alarm 3 OFF delay
H'00000000 to H'000003E7 (0 to 999)
0F30
2F18
Alarm 4 OFF delay
H'00000000 to H'000003E7 (0 to 999)
1000
3000
PV/SP No. 1 Display
Selection
H'00000000 (0):Nothing displayed.
H'00000001 (1):PV/SP
H'00000002 (2):PV
H'00000003 (3):PV/SP (character display)
H'00000004 (4):PV/SP/MV
H'00000005 (5):PV/SP/Multi-SP No.
H'00000006 (6):PV/SP/Soak time remain
H'00000007 (7):PV/SP/Ramp SP
H'00000008 (8):PV/SP/Alarm value 1
1002
3001
MV Display Selection
H'00000000 (0): MV (heating)
H'00000001 (1): MV (cooling)
1006
3003
Automatic Display Return
Time
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
1008
3004
Display Refresh Period
H'00000000 (0):OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
1010
3008
PV/SP No. 2 Display
Selection
H'00000000 to H'00000008 (0 to 8)
Note: Same as PV/SP No. 1 Display Selection.
1012
3009
Valve Opening Monitor
Selection
*2
H'00000000 (0): Measured opening
H'00000001 (1): Estimated opening
Initial setting
1014
300A
Display Brightness
H'00000001 to H'00000003 (1 to 3)
Advanced
function
setting
1016
300B
MV Display
H'00000000 (0): OFF
H'00000001 (1): ON
1018
300C
Move to Protect Level
Time
H'00000001 to H'0000001E (1 to 30)
101E
300F
Auto/Manual Select
Addition
H'00000000 (0): OFF
H'00000001 (1): ON
1022
3011
PV Status Display
Function
H'00000000 (0): OFF
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
H'00000009 (9): Status display message
*1
1024
3012
SV Status Display
Function
H'00000000 to H'00000009 (0 to 9)
Note: Same as for PV Status Display Function.
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
Содержание E5AC
Страница 2: ......
Страница 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 54: ...2 CompoWay F Communications Procedures 2 22 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 96: ...4 Modbus Communications Procedure 4 16 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 114: ...5 Communications Data for Modbus 5 18 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 206: ...6 Programless Communications 6 92 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Страница 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Страница 223: ......