E5AK/E5CK/E5EK
E5AK/E5CK/E5EK
111
ALARM MODE SELECTORS
Alarm outputs are available if they are allocated as outputs. Factory setting is “2: Upper-limit alarm (deviation).”
Setting
Alarm types
Alarm output
number
When X is positive
When X is negative
1
Upper- and lower-limit alarm (deviation)
X
X
ON
OFF
SP
Always ON
2
Upper-limit alarm (deviation)
X
SP
ON
OFF
X
SP
ON
OFF
3
Lower-limit alarm (deviation)
X
SP
ON
OFF
X
SP
ON
OFF
4
Upper- and lower-limit range alarm (deviation)
X
X
SP
ON
OFF
Always OFF
5
Upper- and lower-limit alarm with standby se-
quence (deviation)
X
X
SP
ON
OFF
Always OFF
6
Upper-limit alarm with standby sequence
(deviation)
X
SP
ON
OFF
X
SP
ON
OFF
7
Lower-limit alarm with standby sequence
(deviation)
X
SP
ON
OFF
X
SP
ON
OFF
8
Absolute-value upper-limit alarm
X
0
ON
OFF
0
ON
OFF
X
9
Absolute-value lower-limit alarm
X
0
ON
OFF
0
ON
OFF
X
10
Absolute-value upper-limit alarm with standby
sequence
X
0
ON
OFF
0
ON
OFF
X
11
Absolute-value lower-limit alarm with standby
sequence
X
0
ON
OFF
0
ON
OFF
X
Note: 1. A deviation is defined as deviation from SP.
2. An absolute alarm is defined as a fixed value X with reference to 0.
3. Standby sequence is defined as having the alarm outputs inactive until SP is reached on the initial power up of the Controller.
After SP has been reached, alarms will function normally.
Deviation Alarm
If the alarm mode selector is set to a number between 1 to 7,
alarm values are set to the width deviated from the set point as
shown in the following illustration.
Set point (SP)
100
°
C/
°
F
Alarm value = 10
°
C/
°
F
110
°
C/
°
F
Absolute Alarm
If the alarm mode selector is set to 8 or 9, alarm values are set to
the absolute value based on 0
°
C/
°
F as shown in the following
illustration.
Set point (SP)
325
°
C/
°
F
Alarm value = 328
°
C/
°
F
328
°
C/
°
F