Safety Precautions

Refer to 

Warranty and Limitations of Liability

.

This product is not designed or rated for ensuring 
safety of persons either directly or indirectly.
Do not use it for such purposes.

Do not use this product under ambient conditions that exceed the 
ratings.

 Design

Influence of Surrounding Metal

When mounting the Sensor within a metal panel, ensure that the 
clearances given in the following table are maintained. Failure to 
maintain these distances may cause deterioration in the performance 
of the Sensor. 

Influence of Surrounding Metal 

(Unit: mm)

Mutual Interference

When installing Sensors face-to-face or side-by-side, ensure that the 
minimum distances given in the following table are maintained.

Mutual Interference 

(Unit: mm)

Note: Values in parentheses apply to Sensors operating at different frequencies. 

 Mounting

x

Refer to the following table for the 
torque and tightening ranges 
applied to mount the E2EC-C 
Unthreaded Cylindrical Model. 
Tightening must be as given in 
the following table. 

Permissible Tightening Range and Torque

x

The tightening torque applied to the E2EC-
X4D

@

 Threaded Cylindrical Models must be 

12 N·m max. 

Amplifier Mounting Bracket for DC 2-Wire Models

Mounting

1. Insert the Amplifier into the trapezoidal end (i.e., the fixing side) of 

the Mounting Bracket. 

2. Press the other end of the Amplifier onto the Bracket.

Dismounting

1. Lightly press the hook on the Mounting Bracket with a flat-blade 

screwdriver. 

2. The Amplifier will be automatically released due to the spring force 

of the Mounting Bracket. 

WARNING

Precautions for Correct Use

Model

Item

l

d

D

m

n

E2EC-CR8D

@

0

3

0

2.4

6

E2EC-C1R5D

@

5.4

4.5

10.8

E2EC-C3D

@

8

9

16

E2EC-X4D

@

12

12

24

E2EC-CR5C1

3

1.5

5

E2EC-C2R5C1

8

10

21

d dia.

D

m

l

n

m

l

Model

Item

A

B

E2EC-CR8D

@

18 (4)

6 (3)

E2EC-C1R5D

@

15 (8)

10.8 (5.4)

E2EC-C3D

@

30 (15)

16 (8)

E2EC-X4D

@

40 (20)

24 (12)

E2EC-CR5C1

20 (10)

15 (3)

E2EC-C2R5C1

40 (20)

25 (15)

Model

Tightening 

Set screw tightening 

E2EC-CR8D

@

6 to 10 mm

0.49 N·m

E2EC-C1R5D

@

8 to 16 mm

E2EC-C3D

@

0.98 N·m

E2EC-CR5C1

6 to 16 mm

0.39 N·m

E2EC-C2R5C1

8 to 16 mm

A

B

A

Dimpled
end of set 
screw (M3)

1

2

Amplifier

Cable

Mounting Bracket

1

Flat-blade

screwdriver

2

http://www.ia.omron.com/

6

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

Содержание E2EC -

Страница 1: ...e also available The model numbers are E2EC 5 example E2EC CR8D15 DC 3 Wire Models Models with different frequencies are also available The model numbers are E2EC 5 example E2EC CR5D15 Accessories Ord...

Страница 2: ...proaching D1 Models NO D2 Models NC Refer to the timing charts under I O Circuit Diagrams on page 5 for details NO Refer to the timing charts under I O Circuit Diagrams on page 5 for details Protectio...

Страница 3: ...nce X mm Distance Y mm Sensing Head Y X 4 3 2 1 0 3 1 2 0 1 2 3 4 4 Distance X mm Distance Y mm Sensing Head Y X 6 5 4 3 2 1 0 4 2 0 2 4 Distance Y mm Distance X mm Sensing Head Y X 0 6 0 5 0 4 0 3 0...

Страница 4: ...er Brass Distance X mm Side length of sensing object d mm Stainless steel SUS304 Iron X 5 4 3 2 1 0 5 35 30 25 15 20 10 d d t 1 mm Distance X mm Side length of sensing object d mm Brass Copper Stainle...

Страница 5: ...tor green Operation indicator red Control output 0 V V Load Brown Blue Prox imity Sensor main circuit Note The load can be connected to either the V or 0 V side 0 100 Sensing object Rated sensing dist...

Страница 6: ...Permissible Tightening Range and Torque x The tightening torque applied to the E2EC X4D Threaded Cylindrical Models must be 12 N m max Amplifier Mounting Bracket for DC 2 Wire Models Mounting 1 Insert...

Страница 7: ...8 25 5 35 5 18 8 dia 5 4 24 2 1 10 3 6 1 6 dia shielded robotics cable Standard length 400 mm 2 9 dia vinyl insulated round robotics cable with 2 conductors Conductor cross section 0 15 mm2 Insulator...

Страница 8: ...round cable with 3 conductors Conductor cross section 0 2 mm2 Insulator diameter 1 2 mm Standard length 2 m 2 The cable can be extended up to 50 m separate metal conduit 3 2 5 dia shielded cable Stan...

Страница 9: ...t The load short circuit protection function op erates when the power supply is connected with the correct polarity and the power is within the rated voltage range DC 3 Wire NPN Output Sensors DC 2 Wi...

Страница 10: ...stive load Non contact control system Inductive load Relay solenoid etc Steady state current inrush current Operating reset voltage current Lamp load Steady state current inrush current Open close fre...

Страница 11: ...or is affected by magnetism or static capacitance from an adjacent Sensor and the output is unstable One means of avoiding interference when mounting Proximity Sensors close together is to alternate S...

Страница 12: ...o do not use a Proximity Sensor to turn the power supply ON and OFF for electronic devices that use DC half wave rectification In such a case use a relay to turn the power supply ON and OFF and check...

Страница 13: ...sert the front of the Sensor into the special Mounting Bracket included or DIN Track 2 Press the rear of the Sensor into the special Mounting Bracket or DIN Track When mounting the side of the Sensor...

Страница 14: ...in series with an AND circuit the limit is three Sensors Be careful of the VS value in the diagram at left OR parallel connection In general it is not possible to use two or more Proximity Sensors in...

Страница 15: ...M1J T is 5 V Model Type of connection Connection Description DC 3 wire AND series connection Keep the number of connected Sensors N within the range of the following equation iL N 1 i Upper limit of...

Страница 16: ...or hot concentrated sulfuric acid Maintenance and inspection Periodic Inspection To ensure long term stable operation of the Proximity Sensor inspect for the following on a regular basis Conduct these...

Страница 17: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syst...

Отзывы: