41
Maintenance Functions of DST1-series Safety I/O Terminals
Section 1-7
1-7-6
Monitoring the Operation Time
Description
A DST1-series Safety I/O Terminal measures the time from when a safety out-
put turns ON until the safety input turns ON and internally saves the data in
non-volatile memory. If the value of the operation time reaches the threshold
value, the Threshold Response Time Flag in General Status will turn ON.
• Measurement time: 0 to 65,535 ms (stored data: 0000 to FFFF hex)
• Measurement unit: ms
The input reaction time and the output reaction time of the DST1-series
Safety I/O Terminal are added to monitor the operation time.
Maximum input reaction time of the DST1-series Safety I/O Terminal
= 16.2 ms + ON/OFF delay
Maximum output reaction time of the DST1-series Safety I/O Terminal
= 6.2 ms + Relay reaction time (DST1-MRD08SI-1 only)
The measurement is accurate to ±6 ms.
The user can monitor this information using the Network Configurator and
explicit messages.
Measured
time
Operation time
Safety Input B
(Example: Sensor)
Safety Output A
(Example: Contactor)
Safety I/O Terminal
Safety Output A
(Example: Contactor)
Safety Input B
(Example: Sensor)
ON
OFF
ON
OFF
Contactor operation
time
Measured
time
Содержание DST1-ID12SL-1
Страница 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Страница 2: ......
Страница 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Страница 4: ...iv...
Страница 10: ...x...
Страница 14: ...xiv...
Страница 110: ...86 Remote I O Allocations Section 3 2...
Страница 116: ...92 Indicators Section 4 2...
Страница 134: ...110 DST1 XD0808SL 1 Section 5 4...
Страница 146: ...122 Maintenance Section 7 4...
Страница 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Страница 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Страница 178: ...154 Index...
Страница 181: ...157 Revision History...