129
Examples of Wiring for Each Application
Section 8-2
8-2-5
Limit Switch Dual Channel Inputs and a Manual Reset
An example of the wiring and configuration when using the DST1-ID12SL-1 is
shown below.
Wiring
Configuration
11
12
23
24
S1
E1
S2
S3
GND
E1: 24-V DC Power Supply (S8
@@
)
S1: Safety Limit Switch (D4D or D4B)
(positive opening mechanism)
S2: Limit switch
S3: Reset switch
IN0
T0
T1
IN
11
T1
T2
G
IN1
V
G
Parameter
group
Parameter name
Value
Safety Input 0
0008
Safety Input 0 Channel Mode
Test pulse from test out
0009
Safety Input 0 Test Source
Test Output 0
0054
Dual Channel Safety Input 0/1 Mode
Dual Channel Equivalent
0055
Dual Channel Safety Input 0/1 Discrepancy Time
100 x 10 ms
Safety Input 1
0012
Safety Input 1 Channel Mode
Test pulse from test out
0013
Safety Input 1 Test Source
Test Output 1
Safety Input 11
0052
Safety Input 11 Channel Mode
Used as standard input
0053
Safety Input 11 Test Source
Not Used
0064
Dual Channel Safety Input 10/11 Mode
Single Channel
Test Output 0
0001
Test Output 0 Mode
Pulse Test Output
Test Output 1
0002
Test Output 1 Mode
Pulse Test Output
Test Output 2
0003
Test Output 2 Mode
Power Supply Output
Содержание DST1-ID12SL-1
Страница 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Страница 2: ......
Страница 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Страница 4: ...iv...
Страница 10: ...x...
Страница 14: ...xiv...
Страница 110: ...86 Remote I O Allocations Section 3 2...
Страница 116: ...92 Indicators Section 4 2...
Страница 134: ...110 DST1 XD0808SL 1 Section 5 4...
Страница 146: ...122 Maintenance Section 7 4...
Страница 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Страница 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Страница 178: ...154 Index...
Страница 181: ...157 Revision History...