Step 1: Evaluating the Configuration with Graphs
Section 3-4
3-4
Step 1: Evaluating the Configuration with Graphs
There is a voltage drop in a communications cable as current flows through
the cable. The voltage drop increases in proportion to the length of the com-
munications cable and the amperage of the current being carried.
The communications power supply at each node must be 11 V DC min. The
following graph shows the maximum current that can be supplied through var-
ious lengths of cable while maintaining the minimum voltage required at the
nodes. (The values in the graph provide some extra margin.)
Thick Cable
Thin Cable
Distance (m) 0
25
50
100
150
200
250
300
350
400
450
500
Maximum
current (A)
8.00 8.00 5.42 2.93 2.01 1.53 1.23 1.03 0.89 0.78 0.69 0.63
Distance (m) 0
10
20
30
40
50
60
70
80
90
100
Maximum
current (A)
3.00 3.00 3.00 2.06 1.57 1.26 1.06 0.91 0.80 0.71 0.64
8
7
6
5
4
3
2
1
0
0
50
100
150
200
220
300
350
400
450
500
Max
imum
c
u
rrent
(A
)
Distance (m)
3
2
1
0
0
10
20
30
40
50
60
70
80
90
100
Max
imum
c
u
rrent
(A
)
Distance (m)
Содержание DEVICENET -
Страница 1: ...DeviceNet Cat No W267 E1 11 OPERATION MANUAL...
Страница 2: ...DeviceNet Operation Manual Revised April 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ...viii...
Страница 9: ...x...
Страница 13: ...xiv...
Страница 41: ...20 Basic Operating Procedures Section 1 4...
Страница 107: ...86 Operational Checklist Section 2 6...
Страница 123: ...102 Step 3 Splitting the System into Multiple Power Supplies Section 3 6...
Страница 161: ...140 Index...