D4DS
D4DS
3
Specifications
Approved Standard Ratings
TÜV and BIA (EN60947-5-1)
Utilization category
AC-15
Rated operating current (I
e
)
2 A
Rated operating voltage (U
e
)
400 V
Note:
Use a 10-A fuse type gl or gG as a short-circuit protection device that conforms to IEC269.
UL (UL508/CSA C22.2 No.14)
A600
Rated voltage
Carry current
Current
Volt-amperes
Ca y cu e
Make
Break
Make
Break
120 VAC
10 A
60 A
6 A
7,200 VA
720 VA
240 VAC
30 A
3 A
480 VAC
15 A
1.5 A
600 VAC
12 A
1.2 A
Characteristics
Degree of protection (see note 1)
IP65 (EN60947-5-1)
Life expectancy (see note 2)
Mechanical: 1,000,000 operations min.
Electrical:
150,000 operations min.
Operating speed
0.1 m/s to 0.5 m/s
Contact gap
2 x 2.0 mm min.
Operating frequency
30 operations/minute min.
Positive opening force (see note 3)
58.84 N min.
Positive opening travel (see note 3)
10 mm min.
Insulation resistance
100 M
Ω
min. (at 500 VDC) between terminals of same polarity, between terminals of
different polarity, between each terminal and ground, and between each terminal and
non-current-carrying metal part
Contact resistance
25 m
Ω
max. (initial value)
Dielectric strength
U
imp
4 kV between terminals of same polarity, between terminals of different polarity, and
between each terminal and non-current-carrying metal part (EN60947-5-1)
Rated insulation voltage (U
i
)
400 V (EN60947-5-1)
Conditional short-circuit current
100 A (EN60947-5-1)
Short-circuit protective device (SCPD)
10 A, fuse type gI or gG (IEC269)
Switching overvoltage
1,500 V max. (EN60947-5-1)
Pollution degree
(operating environment)
3 (EN60947-5-1)
Conventional enclosed thermal current
(I
the
)
10 A (EN60947-5-1)
Protection against electric shock
Class II (double insulation)
Vibration resistance
Malfunction: 10 to 500 Hz, 0.65-mm single amplitude with an imposed acceleration of
100 m/s
2
max.
Shock resistance
Destruction: 1,000 m/s
2
min.
Malfunction: 300 m/s
2
min.
Ambient temperature
Operating:
–30
°
C to 70
°
C (with no icing)
Ambient humidity
Operating:
95% max.
Weight
Approx. 76 g (for D4DS-15FS)
Note:
1. Although the Switch casing resists dust, oil, and water, make sure that the keyhole on the head is free from dust, oil, water, and
chemical, otherwise the D4DS may wear out, break, or malfunction.
2. Life expectancy values are calculated at an operating temperature of 5
°
C to 35
°
C, and an operating humidity of 40% to 70%. Con-
tact your OMRON sales representative for more detailed information on other operating environments.
3. These figures are minimum requirements for safe operation.