OMRON
CHAPTER 6 – Functions and Methods
Revision 2.0
Page 71
Remarks
Argument Type
Description
returnstate
bool
Returnstate
is ‘1’ if the function is successful, or ‘0’ otherwise.
TController
string
This is a string representing the name of the temperature
controller.
mode
point
This is a point depicting the mode of operation and defines the
operation to be carried out when a TCAutoTune command is
issued.
0: Indicates that the auto-tuning operation is to be stopped.
1: This mode is supported on the E5*K and is used to set the
limit cycle of the manipulated variable change width to 40%.
2: This is used to start the auto-tuning operation.
Typical Example
temp1 = TCAutoTune(“e5ak”,temp2)
TCBackupMode
Syntax
returnstate = TCBackupMode(TController,mode)
Remarks
Argument Type
Description
returnstate
bool
Returnstate
is ‘1’ if the function is successful, or ‘0’ otherwise.
TController
string
This is a string representing the name of the temperature
controller.
mode
point
This is a point depicting the mode of operation and defines the
method used by a temperature controller for storing internal
variables.
0: In this mode variables are stored in RAM and EPROM.
1: In this mode variables are stored in RAM only.
Typical Example
temp1 = TCBackupMode(“ea5k”,temp2)
TCGetStatusParameter
Syntax
returnstate = TCGetStatusParameter(TController,paramID,value)
Содержание CX-SUPERVISOR - SCRIPT REFERENCE REV2.0
Страница 2: ...CX Supervisor Script Language Software Revision 2 0...
Страница 3: ......
Страница 5: ...CX Supervisor Script Language OMRON Page ii Revision 2 0...
Страница 7: ...CX Supervisor Script Language OMRON Page iv Revision 2 0...
Страница 9: ...CX Supervisor Script Language OMRON Page vi Revision 2 0...
Страница 13: ......
Страница 15: ...CHAPTER 1 Introduction OMRON Page 2 Revision 2 0...
Страница 19: ...CHAPTER 2 Expressions OMRON Page 6 Revision 2 0...
Страница 21: ...CHAPTER 3 Scripts OMRON Page 8 Revision 2 0...
Страница 151: ...CHAPTER 8 Colour Palette OMRON Page 138 Revision 2 0...