312
Indicators and Error Processing
Section 8-1
8-1
Indicators and Error Processing
8-1-1
Errors Occurring in the Slave Unit
The following table lists probable causes and remedies for errors that occur in
the Slave Unit.
8-1-2
C200H I/O Link Unit Seven-segment Display
C200H I/O Link Units have a 2-digit, 7-segment display that normally indi-
cates the C200H I/O Link Unit’s node address (decimal value from 00 to 63).
When an error occurs, the display will alternate between the error code and
the node address of the faulty C200H I/O Link Unit. If more than one error
occurs at the same time, the error codes will be displayed in sequence, fol-
lowed at the end by the faulty Unit’s node address.
Dot Indicators
The dots at the lower-right of each digit are operated by bit 13 (Read/Write
Area default setting) of the Status Area (first word of the IR Area + 5 words),
and show whether user settings or default settings are being used for the
Read/Write Area. The dots are lit when the default settings are used and not
lit when the user settings are used.
Display/Indicator
status
Network status
Probable cause and remedy
MS
NS
ON
(green)
ON
(green)
Remote I/O or message commu-
nications in progress (normal
status)
Remote I/O communications and/or message communications
are active on the Network.
ON
(green)
OFF
Checking for node address dupli-
cation
Checking whether the Unit’s node address has been set on
another node.
ON
(green)
Flashing
(green)
Waiting for connection
The Unit is waiting for a connection from the Master Unit.
ON (red)
OFF
Watchdog timer error
A watchdog timer error occurred in the Unit. Replace the Unit.
Flashing
(red)
OFF
Incorrect switch settings
A mistake has been made in the switch settings. Check the set-
tings and restart the Slave.
ON
(green)
ON
(red)
Node address duplication
The Slave Unit’s node address has been set on another node.
Change the settings to eliminate the duplication and restart the
Slave.
ON
(green)
ON
(red)
Bus Off error detected
The communications controller detected a Bus Off status and
communications have been stopped.
Check the following and restart the Slave: Master/Slave baud
rates, for loose or broken cables, for noise, cable lengths, and
Terminating Resistors.
ON
(green)
Flashing
(red)
Communications timeout
The connection with the Master Unit timed out.
Check the following and restart the Slave: Master/Slave baud
rates, for loose or broken cables, for noise, cable lengths, and
Terminating Resistors.
Normal: C200H I/O Link Unit node address
Error: Error code and faulty C200H I/O Link Unit's node address
Read/Write Area default/user settings
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Содержание CS1W-DRM21
Страница 3: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 7: ...vi Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 11: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 47: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 245: ...228 B7AC Interface Units Section 5 5 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 315: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 337: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 339: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 371: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 373: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 378: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...
Страница 379: ...W347 E1 6 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...