;&'4&'-0)*'")<
Section 3-5
)(
Counting Direction
For every Counter the (up or down) counting direction is indicated and can be
used in the Ladder Program.
3-5
Output Control
Output Control Mode
The 32 Outputs of the High-speed Counter Unit can be controlled automatically in
two ways:
•
Range Mode. In Range Mode you can define up to a maximum of 32 Ranges
per Counter. The Outputs are controlled according to the Counter Value being
within Range Limits. For a detailed description about Range Mode refer to 3-5-
1
•
Comparison Mode. In Comparison Mode you can define up to a maximum of
32 Comparison Values per Counter. The Outputs are controlled according to
the direction in which the Counter Value crosses the Comparison Value. For a
detailed description about Comparison Mode refer to 3-5-2
If the Unit is configured for Range Mode all four Counters will operate in Range
Mode. If the Unit is configured for Comparison Mode all four Counters will operate
in Comparison Mode.
Besides automatically, the Digital Outputs can also be controlled manually (refer
to 3-5-3
).
CNT1:
CNT2:
CNT3:
CNT4:
n+24
n+29
n+34
n+39
Gate Open/Closed:
0 = Gate Closed
1 = Gate Open
Counting Direction:
0 = Counter counts down
1 = Counter counts up
Preset Activated:
ON for exactly one PLC-cycle
Reset Activated:
ON for exactly one PLC-cycle
Capture Activated:
ON for exactly one PLC-cycle
Z-signal Activated:
ON for exactly one PLC-cycle
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
The Reset, Preset, Capture and Z-signal Activated Bits are ON for exactly one PLC-cycle after
the occurrence of a (short) pulse which was detected since the previous I/O Refresh.
General Setting:
m
Output Control Mode:
0 = Range Mode
1 = Comparison Mode
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
W902-E2-03.book Seite 65 Donnerstag, 7. Oktober 2004 2:06 14
Содержание CS1W-CT021
Страница 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Страница 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Страница 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Страница 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Страница 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Страница 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Страница 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...