2-17
2 Basic System Configuration and Devices
CP1E CPU Unit Hardware User’s Manual(W479)
2-3 Expan
sion
I/O U
n
it or Expan
sion
Un
it
2
2-
3-5 R
estr
ictions on System Con
figur
ation
According to the ambient temperature, there are restrictions on power supply voltage and output
load current for the DC-power-supply CPU Units.
Refer to Output Specifications for Relay Outputs in 3-1-3 Common I/O Specifications and in 3-2-4 I/O
Specifications for details.
Use CP1W-32ER/ET/ET1 32-point Output Units with the number of simultaneously ON less than 24
points (75%).
When connecting CP-series Expansion Units or Expansion I/O Units to a CPU Unit with AC power,
provide a space of approximately 10 mm between the CPU Unit and the first Expansion Unit or
Expansion I/O Unit.
If sufficient space cannot be provided between the CPU Unit and the first Expansion Unit or Expan-
sion I/O Unit, use the PLC in an ambient temperature of 0 to 50°C.
Restrictions by ambient temperature
Restrictions on the Number of Simultaneously ON Points
Mounting Restriction
10 mm
CP1E CPU Unit
Expansion I/O Units or Expansion Units