9
.
Program
59
9.4.2. Lists of Allocations
The tables below list the addresses necessary to execute this program.
●CIO area
They are the fixed addresses determined by the unit address (unit number) that is set for
SCU.
Unit number 0 is used in this program.
Address
Data type
Variable name
1519.10
BOOL
SequenceAbortCompletion_SCU_0_P2
1519.11
BOOL
SequenceEndCompletion_SCU_0_P2
1519.15
BOOL
ProtocolMacroExecuting_SCU_0_P2
1519
UINT
ProtocolMacroErrorCode_SCU_0_P2
Additional Information
For details on the CIO area allocated to SCU, refer to
2-3-2. CIO Area
of the
CJ Series Serial
Communications Units OPERATION MANUAL
(Cat. No. W336).
●Related auxiliary area
They are the fixed addresses determined by the communications port number (internal
logical port) specified in the program (PMCR instruction operands).
This program uses the communications port No. 7.
Address
Data type
Variable name
A202.07
BOOL
CommPortEnabledFlag_P7
Additional Information
For information on the related auxiliary area for the PMCR instruction, refer to
Related
Auxiliary Area Words and Bits
in
Serial Communications Instructions (PMCR)
in
SECTION 3.
Instructions
of the
CJ Series Programmable Controllers INSTRUCTIONS REFERENCE
MANUAL
(Cat. No. W474).
Содержание CJ2H-CPU64 -
Страница 81: ...78...
Страница 82: ...2016 0616 P652 E1 01...