9
< I/O Units and CPU Bus Units>
Unit name
C200H-series Unit
CJ-series Unit
Description
Communication Unit
[CompoBus/S]
C200HW-SRM21(-V1)
[CompoBus/S]
CJ1W-SRM21
There are some remarks to be followed
when CS1W-SRM21 is used.
Refer to the
C200HW/CS1W/CJ1W/CQM1/SRT1/SRT2
CompoBus/S OPERATION MANUAL
(Cat.
No. W266) for details.
[DeviceNet]
C200HW-DRM21(-V1)
[DeviceNet]
CJ1W-DRM21
There are also some remarks to be followed
when CS1W-DRM21 is used.
Refer to the
CS1W-DRM21(-V1),CJ1W-DRM21 CS/CJ
SERIES DeviceNet UNITS OPERATION
MANUAL (Cat. No. W380)
for details.
[SYSMAC BUS]
Wired: C200H-RM201
Optical: C200H-RM001-PV1
[SYSMAC BUS]
None
[CompoNet]
CJ1W-CRM21
[DeviceNet]
CJ1W-DRM21
[CompoBus/S]
CJ1W-SRM21
SYSMAC BUS cannot be used with the
CJ2-series CPU Unit.
We recommend you to use left networks
instead.
Refer to the
CS/CJ series CompoNet Master
Units OPERATION MANUAL
(Cat. No.
W456) and
CompoNet Slave Units and
Repeater Unit OPERATION MANUAL
(Cat.
No. W457) for details of CompoNet.
Refer to the
CS1W-DRM21(-V1),CJ1W-DRM21 CS/CJ
SERIES DeviceNet UNITS OPERATION
MANUAL
(Cat. No. W380) for details of
DeviceNet.
Refer to the
C200HW/CS1W/CJ1W/CQM1/SRT1/SRT2
CompoBus/S OPERATION MANUAL
(Cat.
No. W266) for details of CompoBus/S.
[PC Card Unit]
C200HW-PCU01
C200HW-PCS01-V1
[PC Card Unit]
None
[Memory card]
HMC-
EF□□□
[Ethernet]
CS1W-ETN21
[EtherNet/IP]
CS1W-EIP21
The PC Card Unit cannot be used with the
CJ2-series CPU Unit.
Insert the memory card into the CJ2-series
CPU Unit to transfer data in PLC memory
between the CPU Unit and memory card.
Moreover, communications can be made
with the Ethernet Unit or EtherNet/IP Unit.
Содержание CJ2H-CPU6 Series
Страница 7: ...MEMO...
Страница 38: ...P075 E1 04 2011 0119 0511...