3 Memory Allocations
3 - 12
CJ-series EtherCAT Slave Units Operation Manual (W541)
Setting Results Codes
m + 4
00 to 15
First word in IN
data area
User
0000 hex
Set the starting word of the IN
data area. Setting ranges vary
by IN data area type.
• CIO: 0000 to 17FF hex
• DM: 0000 to 7FFF hex
• WR: 0000 to 01FF hex
• HR: 0000 to 01FF hex
• EM: 0000 to 7FFF hex
*1
m + 5
00 to 15
IN data area size
User
0000 hex
Set the IN data area size in bytes
from one of the following.
• 00 hex: 0 byte
• 32 hex: 50 byte
• 64 hex: 100 byte
• C8 hex: 200 byte
• 190 hex: 400 byte
m + 6
00 to 15
Setting results
Unit
0000 hex
Display the setting results.
Refer to
on page 3-12 for the code.
*1. EM areas are not available for all CJ-series CPU Units. Refer to the operation manuals of the CPU Units for
details on the EM memory area specification.
Result code
Description
Corrective action
0000 hex
*1
*1. If the EtherCAT Slave Unit is set with default values, the setting result code will be 0000 hex and the Unit can-
not perform process data communications with the EtherCAT master.
Completed normally.
---
1101 hex
Incorrect area setting.
Ensure that the memory area codes for OUT
data area type and IN data area type are set
to the allowable values.
1103 hex
The first word is outside the setting range.
Ensure that the first word in OUT data area
and first word in IN data area are set as valid
memory areas for the corresponding memory
area type set with the OUT data area type
and IN data area type codes.
1104 hex
The allocated data area exceeds the valid
word range.
Ensure that the OUT data area range and IN
data area range setting does not exceed
valid memory locations for the corresponding
memory area type set with the OUT data
area type and IN data area type codes.
110C hex
The area size is outside the setting range.
Ensure that the OUT data area size and IN
data area size are set to allowable values for
the corresponding memory area type set with
the OUT data area type and IN data area
type codes.
Word
Bit
Name
Manipulated by Default value
Function
Содержание CJ1W- ECT21
Страница 1: ...Cat No W541 E1 02 OPERATION MANUAL SYSMAC CJ Series CJ1W ECT21 EtherCAT Slave Unit ...
Страница 8: ...CONTENTS 6 CJ series EtherCAT Slave Units Operation Manual W541 ...
Страница 30: ...Revision History 28 CJ series EtherCAT Slave Units Operation Manual W541 ...
Страница 32: ...Sections in this Manual 30 CJ series EtherCAT Slave Units Operation Manual W541 ...
Страница 148: ...Appendices A 34 CJ series EtherCAT Slave Units Operation Manual W541 ...
Страница 149: ...I 1 I CJ series EtherCAT Slave Units Operation Manual W541 Index ...
Страница 152: ...I 4 CJ series EtherCAT Slave Units Operation Manual W541 Index ...
Страница 153: ......