4-15
4 Message Communications
CJ-series User Defined CAN Unit Operation Manual for NJ-series CPU Unit (W517)
4-2 Un
it C
onf
igu
ratio
n an
d Co
ntro
l
4
4-
2-4 C
onfigu
re 1
1-
B
it ID
Input Message Buf
fer (2
905)
The following table defines the minimum and maximum values for each item in the command block with
setting details.
Issuing a Configure 11-Bit ID Input (Receive) Message Buffer command will result in the following
response End Codes.
Setting
Minimum Value (Hex)
Maximum Value (Hex)
Setting Details
Buffer Number
0000
027F
Defines which buffer to
configure (0 to 639)
Identifier 11-bit
0000
07FF
Identifier value
Big or Little Endian
0000
0001
•
0000: Big Endian
•
0001: Little Endian
Response Block
End Code (hex)
Description
Condition
Correction
No response
---
Unit state = ST1 or ST2
Restart the CPU, make sure
that the unit is mounted and
wired correctly
0000
1
Normal completion
Unit state = ST4 or ST5 and
all parameters are in range
Command is executed and
operation is normal.
1001
Command length exceeds
maximum command length
---
Too many parameters sent in
the command.
Correct the command and re-
send.
1002
The command length is
insufficient for the smallest
command
---
Too few parameters sent in
the command.
Correct the command and re-
send.
1103
Address range destination
error
Unit state = ST4 or ST5 and
buffer number is greater than
or equal to the number of
input buffers configured with
command 2902
Number of input buffers
exceeds the number of input
buffers configured by mes-
sage command 2902.
Increase the number of input
buffers with message com-
mand 2902 or select a input
buffer, smaller than the maxi-
mum of input buffers config-
ured by message command
2902.
110C
Parameter error
Unit state = ST4 or ST5 and
one or more parameters are
not in range
Correct the parameters.
2201
Not executable in current
mode
Unit state = ST3
Nothing configured, please
perform message command
2902 before executing this
command.
05
29
Command
Code
End
Code
Содержание CJ1W-CORT21
Страница 2: ......
Страница 116: ...5 Communications Timing 5 10 CJ series User Defined CAN Unit Operation Manual for NJ series CPU Unit W517...
Страница 134: ...6 Troubleshooting and Maintenance 6 18 CJ series User Defined CAN Unit Operation Manual for NJ series CPU Unit W517...
Страница 140: ...Appendices A 6 CJ series User Defined CAN Unit Operation Manual for NJ series CPU Unit W517...
Страница 141: ...Index 1 CJ series User Defined CAN Unit Operation Manual for NJ series CPU Unit W517 I Index...
Страница 144: ...Index 4 CJ series User Defined CAN Unit Operation Manual for NJ series CPU Unit W517 Index...