6
XW2Z-S011
CS1W-OD231
C200H-OD215
Reused cable
C200H-OD215
CS1W-OD231
Remarks
Rated voltage
5 to 24 VDC
12 to 24 VDC
Use CS1W-MD561 when using 5 VDC.
Max. switching capacity
16 mA/4.5 VDC to
100 mA/26.4 VDC
0.8 A/common,
3.2 A/Unit
0.5 A/point,
2.5 A/common, 5 A/Unit
Leakage current
0.1 mA max.
0.1 mA max.
Residual voltage
0.7 V max.
1.5 V max.
Make sure that the connected device operates
correctly.
ON response time
0.2 ms max.
0.5 ms max.
Make sure that the connected device operates
correctly.
OFF response time
0.6 ms max.
1 ms max.
Make sure that the connected device operates
correctly.
No. of circuits
8 points/common x
4 circuits (32 outputs)
16 points/common x
2 circuits (32 outputs)
The number of circuits decreased from 4 to 2.
Rewire if separate power supplies are used.
Fuses
4 (1 fuse/common)
None
When protection is required, connect a protective
device externally.
External power supply
5 to 24 VDC±10%,
90 mA min.
2.8 mA x no. of ON outputs
10.2 to 26.4 VDC
Dynamic outputs
30 mA min.
Not supported
Dynamic outputs are not supported.
* CN1 COM0 and COM1 and
CN2 COM2 and COM3 are
internally connected in the
CS1-series Unit. When
separate power supplies were
used, rewire to use one
common power supply.