7 Using an optional card
7-2 Optional card
BU5002R/BU3002R/BU3002RH
121
7
7-2 Optional card
7-2-1 Contact signal I/O card (SC08)
The customer can automate processing in the event of a power outage by developing a
system on their own with contact signal inputs and outputs. It is possible to perform
processing for a power outage by detecting a backup signal and perform system shutdown
processing by detecting a low battery level signal.
In addition, by inputting a backup stop signal from the system, it is possible to stop the UPS
while the battery still remains, and become ready for the next occurrence of power outage.
On this UPS, the standard contact signal I/O port and the optional relay output type contact
I/O card (SC08) contact signal input/output can be used.