ATEG Automation GmbH
|
Intzestraße 50
|
42859 Remscheid
|
Germany
|
Tel.: +49 (0)2191 / 591457-0
|
|
www.ateg.de
Datenblatt
Zeitrelais H3DT
H3DT
H3DT-F
18
Characteristics
I/O
Input
None
Output
Control output
Output is turned ON/OFF according to the time set on the ON time
setting dial and OFF time setting dial.
Installation Pitch and Output
Switching Capacity (Reference
Values)
The relation between the installation pitch and
the load current is shown in the following
graph.
If Timer is used under load conditions that
exceed the specified values, the temperature
inside the Timer will increase, reducing the life
expectancy of internal parts.
Ambient temper
ature (°C)
Mounting interval (mm)
80
70
60
50
40
30
20
10
0
5 10 15 20 25 30
DIN Track
Timer installation pitch: d
Tested Timer: H3DT-F
Applied voltage: 240 VAC
Installation pitch: 0 and 10 mm
Load current: 5 A
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method
Applicable standards
*
Certification is pending for DNV GL.
Accuracy of operating
time
1% of FS max. (
1%
10 ms max. at 1.2-s range)
Setting error
10% of FS
0.05 s max.
Influence of voltage
0.5% of FS max. (
0.5%
10 ms max. at 1.2-s range)
Influence of
temperature
2% of FS max. (
2%
10 ms max. at 1.2-s range)
Insulation resistance
100 M
min. at 500 VDC
Dielectric strength
Between charged metal part and operating section: 2,900 VAC 50/60 Hz for 1
min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for 1 min.
Impulse withstand
test voltage
5 kV between power terminals, 7.4 kV between conductor terminal and
operating section
Noise immunity
Square-wave noise generated by noise simulator (pulse width: 100 ns/1
s,
1-ns rise):
1.5 kV
Static immunity
Malfunction: 4 kV, Destruction: 8 kV
Vibration
resistance
Destruction
0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction
0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock
resistance
Destruction
1,000 m/s
2
3 times each in 6 directions
Malfunction
100 m/s
2
3 times each in 6 directions
Life
expectancy
Mechanical
10 million operations min. (under no load at 1,800 operations/h)
Electrical
100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Degree of protection
IP30 (Terminal block: IP20)
Weight
Approx. 90 g
Safety
standards
cULus: UL 508/CSA C22.2 No. 14
EN 61812-1: Pollution degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section GB 14048.5
LR: Category ENV1.2
DNV GL
*
EMC
(EMI)
EN 61812-1
Radiated Emissions:
EN 55011 class B
Emission AC Mains:
EN 55011 class B
Harmonic Current:
EN 61000-3-2
Voltage Fluctuations and Flicker:
EN 61000-3-3
(EMS)
EN 61812-1
Immunity ESD:
EN 61000-4-2
Immunity RF-interference:
EN 61000-4-3
Immunity Burst:
EN 61000-4-4
Immunity Surge:
EN 61000-4-5
Immunity Conducted Disturbance:
EN 61000-4-6
Immunity Voltage Dip/Interruption:
EN 61000-4-11
Erstellt am 09.10.2020 um 23:38 Uhr | Alle Angaben ohne Gewähr, Irrtümer und Änderungen vorbehalten!
Seite 19 von 37