30
Multi-function output
terminal P1 selection
1114h
C021
1415h
C021
Relay output (MA, MB)
function selection
1119h
C026
141Ah
C026
AM selection
111Bh
C028
00: F (Output frequency)
01: A (Output current)
-
141Ch
C028
00: Output frequency
01: Output current
02: Output torque
04: Output voltage
05: Input power
06: Electronic thermal load rate
07: LAD frequency
10: Cooling fin temperature
11: Output torque (signed)
13: DriveProgramming (YA(1))
16: Option (No applicable Option)
-
Multi-function output
111Dh
C031
141Fh
C031
Relay output (MA, MB)
1122h
C036
1424h
C036
Light load signal output
mode
1178h
C038
00: Enabled during acceleration/
deceleration/ constant speed
01: Enabled only during constant
speed
-
1426h
C038
00: During acceleration/
deceleration and constant speed
01: Only during constant speed
-
Light load detection level
1179h
C039
0 to 20000
0.01[%]
1427h
C039
0~2000
0.1[%]
Overload warning level
1124h
C041
1429h
C041
2nd overload warning level
153Ah
C241
2429h
C241
142Ah C042(HIGH)
142Bh C042(LOW)
142Ch C043(HIGH
142Dh C043(LOW)
PID deviation excessive
1129h
C044
0 ~ 1000
0.1[%]
142Eh
C044
0~1000
0.1[%]
0.01[Hz]
Arrival frequency during
deceleration
1128h
C043
0 to 20000
Set to10000 at rated current
0.01[%]
0~2000
0.1[%]
Arrival frequency during
acceleration
1126h
C042
0 ~ 4000
0.1[Hz]
0~40000 (In the high-frequency
mode︓58000)
00: RUN
01: FA1
02: FA2
03: OL
04: OD
05: AL
06: Dc
07: FBV
08: NDc
09: LOG
10: ODc(Do not use.)
43: LOC
-
00: RUN (During RUN)
01: FA1 (Constant speed arrival
signal)
02: FA2 (Set frequency exceeded
signal)
03: OL (Overload warning)
04: OD (Excessive PID deviation)
05: AL (Alarm signal)
06: FA3 (Set-frequency only signal)
07: OTQ (Overtorque/Undertorque
signal)
09: UV (Signal during undervoltage)
10: TRQ (Torque limit)
11: RNT (RUN time over)
12: ONT (Power ON time over)
13: THM (Electronic thermal
warning)
19: BRK (Brake release)
20: BER (Brake error)
21: ZS (0-Hz detection signal)
22: DSE (Excessive speed deviation)
23: POK (Position ready)
24: FA4 (Set frequency exceeded
signal 2)
25: FA5 (Set-frequency only signal
2)
26: OL2 (Overload warning 2)
27: FVDc (Analog FV disconnection
detection)
28: FIDc (Analog FI disconnection
detection)
31: FBV (PID feedback comparison)
32: NDc (Communications
disconnection detection)
33: LOG1 (Logic operation output 1)
34: LOG2 (Logic operation output 2)
35: LOG3 (Logic operation output 3)
39: WAC (Capacitor life warning)
40: WAF (Cooling fan life warning)
41: FR (Starting contact signal)
42: OHF (Cooling fin overheat
warning)
43: LOC (Low current signal)
44: MO1 (General-purpose output 1)
45: MO2 (General-purpose output 2)
46: MO3 (General-purpose output 3)
50: IRDY (Operation ready)
51: FWR (Forward run)
52: RVR (Reverse run)
53: MJA (Fatal fault signal)
54: WCFV (Window comparator FV)
55: WCFI (Window comparator FI)
58: FREF (Frequency reference
source)
59: REF (RUN command source)
60: SETM (Motor 2 selection)
62: EDM (Safety device monitor
signal)
63: OPO (Option)
255: no (No allocation)
-
00︓NO
01︓NC
-
00: NO (NO contact)
01: NC (NC contact)
-