background image

27 

FI start selection

1085h

A105

00: Start frequency A101

01: 0 Hz

-

1287h

A105

00: FI Start Frequency (A101)

01: 0 Hz

-

Operation frequency input A

setting

108Eh

A141

12AFh

A141

Operation frequency input B

setting

108Fh

A142

12B0h

A142

Operator selection

1090h

A143

00: Addition (A + B)

01: Subtraction (A − B)

02: Multiplication (A × B)

-

12B1h

A143

00: Addition (A141 + A142)

01: Subtraction (A141 − A142)

02: Multiplication (A141 × A142)

-

12B3h A145(HIGH)

12B4h A145(LOW)

Frequency addition direction

1093h

A146

00: Adds the A145 value to the

output

-

12B5h

A146

00: Frequency ref A145

01: Frequency reference − A145

-

12C6h A161(HIGH)

12C7h A161(LOW)

12C8h A162(HIGH)

12C9h A162(LOW)

VR start ratio

1098h

A153

0 ~ 100

1[%]

12CAh

A163

0 to VR End Ratio

1[%]

VR end ratio

1099h

A154

0 ~ 100

1[%]

12CBh

A164

VR Start Ratio to 100

1[%]

VR start selection

109Ah

A155

0, 1

-

12CCh

A165

00: VR Start Frequency (A161)

01: 0 Hz

-

Retry selection

10A5h

b001

00: Alarm

01: 0 Hz start

02: Frequency matching restart

03: Trip after frequency matching

deceleration stop

-

1301h

b001

00: Trip

01: 0-Hz restart

02: Frequency matching restart

03: Trip after frequency matching

deceleration stop

04: Frequency pull-in restart

-

Allowable momentary power 10A6h

b002

3 ~ 250

0.1[s]

1302h

b002

3~250

0.1[s]

Retry wait time

10A7h

b003

3 ~ 1000

0.1[s]

1303h

b003

3~1000

0.1[s]

Momentary power

interruption/undervoltage

trip during stop selection

10A8h

b004

00: Disabled

01: Enabled

-

1304h

b004

00: Disabled

01: Enabled

02: Disabled during stop and

deceleration stop by turning off the

RUN command

-

Momentary power

interruption retry time

10A9h

b005

00: 16 times

01: No limit

-

1305h

b005

00: 16 times

01: No limit

-

Starting frequency at

frequency pull-in restart

1170h

b011

00: Frequency at interruption

01: Max. frequency

02: Set frequency

-

131Fh

b030

00: Frequency at interruption

01: Maximum frequency

02: Set frequency (Frequency

reference)

-

Electronic thermal level

10ADh

b012

130Dh

b012

2nd electronic thermal level

1527h

b212

230Ch

b212

Electronic thermal

characteristics selection

10AEh

b013

130Eh

b013

2nd electronic thermal

characteristics selection

1528h

b213

230Dh

b213

Overload limit selection

10B5h

b021

1316h

b021

2nd overload limit selection

1529h

b221

2316h

b221

Overload limit level

10B6h

b022

1317h

b022

2nd overload limit level

152Ah

b222

2317h

b222

Overload limit parameter

10B7h

b023

1318h

b023

2nd overload limit parameter 152Bh

b223

2318h

b223

Deceleration rate constant

1171h

b029

1 ~ 30000

0.1[s]

131Eh

b029

1~30000

0.1[s]

Frequency pull-in restart

1172h

b030

200 ~ 20000

0.01[%]

131Dh

b028

200~2000

0.1[%]

Soft lock selection

10BCh

b031

00: Data other than b031 cannot be

changed when terminal SFT is ON.

01: Data other than b031 and the

specified frequency parameter

cannot be changed when terminal

SFT is ON.

02: Data other than b031 cannot be

changed.

03: Data other than b031 and the

specified frequency parameter

cannot be changed.

10: Data other than parameters

changeable during operation cannot

be changed.

-

1320h

b031

00: Data other than b031 cannot be

changed when terminal SFT is ON.

01: Data other than b031 and the

set frequency cannot be changed

when terminal SFT is ON.

02: Data other than b031 cannot be

changed.

03: Data other than b031 and set

frequency cannot be changed.

10: Data can be changed during

RUN.

-

Selection of non-stop

function at momentary

power interruption

10C9h

b050

00: Disabled

01: Enabled (Stop)

02: Enabled (Restart)

-

1334h

b050

00: Disabled

01: Enabled (Deceleration stop)

02: Enabled (Constant voltage,

without recovery)

03: Enabled (Constant voltage, with

recovery)

-

Starting voltage of non-stop

function at momentary

power interruption

10CAh

b051

0 ~ 10000

0.1[V]

1335h

b051

0~10000

0.1[V]

Stop deceleration level of

non-stop function at

momentary power

interruption

10CBh

b052

0 ~ 10000

0.1[V]

1336h

b052

0~10000

0.1[V]

1337h b053(HIGH)

1338h b053(LOW)

Deceleration starting width

of non-stop function at

momentary power

interruption

10CEh

b054

0 ~ 100

0.1[Hz]

1339h

b054

0~1000 (In the high-frequency

mode︓10000)

0.01[Hz]

Overvoltage protection

proportional gain during

deceleration

1173h

b055

2 ~ 50

0.1

1388h

b133

0~500

0.01

Overvoltage protection

integral time during

deceleration

1174h

b056

0 ~ 1500

0.1[s]

1389h

b134

0~1500

0.1[s]

0.01[s]

1 ~ 300

0.1[s]

1~30000

0.1[s]

Deceleration time of nonstop

function at momentary

10CCh

b053

1 ~ 30000

0.1[s]

1~360000

00: Disabled

01: Enabled in acceleration/constant

-

00: Disabled

01: Enabled during

-

00: Disabled

01: Enabled in acceleration/constant 0.01[%]

200~2000

0.1[%]

0.01[Hz]

2000 to 10000

Set the rated current to 10000

0.01[%]

200~1000

0.1[%]

00: Reduced torque characteristics 1

01: Constant torque characteristics

02: Reduced torque characteristics 2

-

00: Reduced torque characteristics

01: Constant torque characteristics

02: Free setting

-

VR end frequency

1097h

A152

0 ~ 4000

0.1[Hz]

0~40000 (In the high-frequency

mode︓~58000)

0.01[Hz]

VR start frequency

1095h

A151

0 ~ 4000

0.1[Hz]

0~40000 (In the high-frequency

mode︓~58000)

0.01[Hz]

00: Digital Operator (F001)

01: Digital Operator (volume)

02: Input FV

03: Input FI

04: RS485 communications

-

00: Digital Operator (A020/A220)

01: Volume

02: Voltage (FV) input

03: Current (FI) input

04: Modbus communication

05: Option

07: Pulse train frequency

-

Frequency addition amount

1091h

A145

0 ~ 4000

0.1[Hz]

0~40000 (In the high-frequency

mode︓~58000)

 

Содержание 3G3JX

Страница 1: ...Simple Compact Inverters JX series Replace Guide From 3G3JX to 3G3MX2 3G3MX2 A 3G3JX A I924 E1 01...

Страница 2: ...ith respect to the use of the information contained herein Moreover because OMRON is constantly striving to improve its high quality products the information contained in this manual is subject to cha...

Страница 3: ...afe use and precautions for correct use Intended Audience This guide is intended for the following personnel Personnel in charge of introducing control equipment Personnel in charge of designing contr...

Страница 4: ...ity or the results from the use of Products in combination with any electrical or electronic components circuits system assemblies or any other materials or substances or environments Any advice recom...

Страница 5: ...Liability Change in Specifications Product specifications and accessories may be changed at any time based on improvements and other reasons It is our practice to change part numbers when published r...

Страница 6: ...derstand the manuals for all devices and equipment that will make up the system to ensure that the system is used safely Review the entire contents of these manuals including all safety precautions pr...

Страница 7: ...to install and wire the inverter set parameters needed to operate the inverter and remedies to be taken and inspection methods to be used in case that problems occur 3G3MX2 Series Type V1 Multi functi...

Страница 8: ...History A manual revision code appears as a suffix to the catalog number on the front and back covers of the manual Revision code Date Revised content 01 July 2019 Original production Cat No I924 E1 0...

Страница 9: ...al Dimensions 13 4 Arrangement and Function of Terminal Block 17 4 1 Control Circuit Terminal Block 17 5 Functional difference 19 5 1 Dual duty rating 19 5 2 Modbus communication 19 6 Parameter List 2...

Страница 10: ...10 1 Target model 1 Replaced old model 3G3JX series Compact Simplified Inverter 3G3JX 2 New model 3G3MX2 Series Type V1 Multi function Compact Inverter 3G3MX2 V1...

Страница 11: ...ferences between 3G3JX and 3G3MX2 V1 in default parameter values and parameter functions refer to this guide For details of functions refer to related product user s manuals at the time of setting 6 T...

Страница 12: ...140 128 170 5 0 0 4 5 A2055 180 250 169 4 164 235 6 A2055 V1 140 260 155 0 0 6 A2075 180 250 169 4 164 235 6 A2075 V1 140 260 155 0 0 6 3 phase 400 V class 3G3JX Series 3G3MX2 V1 Series Model 3G3JX D...

Страница 13: ...V1 3 phase 200 V input specifications 2 When using 3G3JX AE with single phase 200 V input select from 3G3MX2 V1 single phase 200 V input specifications 3 2 External Dimensions 3G3JX Series 3G3MX2 V1 S...

Страница 14: ...s Model 3G3JX D mm D1 mm D2 mm A4004 130 5 28 2 6 AE007 A2015 157 5 55 6 A2022 A4007 A4015 A4022 AE015 AE022 Model 3G3MX2 D mm D1 mm A4004 V1 143 5 28 A2015 V1 170 5 55 A2022 V1 A4007 V1 A4015 V1 A402...

Страница 15: ...15 3G3JX Series 3G3MX2 V1 Series Model 3G3JX A2037 A4037 Model 3G3MX2 A2037 V1 A4040 V1...

Страница 16: ...16 3G3JX Series 3G3MX2 V1 Series Model 3G3JX A2055 A2075 A4055 A4075 Model 3G3MX2 A2055 V1 A2075 V1 A4055 V1 A4075 V1...

Страница 17: ...ared with the safety input When the safety function selector switch is ON S3 and S4 are automatically set to safety input GS1 GS2 S5 Multi function input S5 TH Multi function input External thermistor...

Страница 18: ...1 Multi function output terminal Safety monitor terminal used in common This terminal is automatically set to P1 EDM Safety monitor signal when the EDM function selector switch is turned ON PC Output...

Страница 19: ...torque during acceleration and deceleration Light load VT This mode is for a fan pump or other device that operates at the rated motor torque or lower With a load tolerance of 120 of rated torque min...

Страница 20: ...rameter arrangement parameter name and default value There are some difference of Parameter name settings number date range and arrangement between 3G3JX and 3G3MX2 V1 Before setting to refer this sec...

Страница 21: ...nd control 9 2CH 2 step acceleration deceleration 2CH 2 step acceleration deceleration 11 FRS free run stop FRS Free run stop 12 EXT external trip EXT External trip 13 USP USP function UPS Power recov...

Страница 22: ...3MX2 V1 Data No Code Function name Code Function name 0 RUN signal during RUN RUN Signal during RUN 1 FA1 constant speed arrival signal FA1 Constant speed arrival signal 2 FA2 over set frequency arriv...

Страница 23: ...008h 0008h 0007h Multi function Input 3 0009h 0009h 0008h Multi function Input 4 000Ah 000Ah 0009h Multi function Input 5 000Bh 000Bh 000Ah Operation status 1 Run 0 Stop Interlocked with d003 000Eh 00...

Страница 24: ...01Ch Fault Monitor 1 Fault 001Dh Fault Monitor 1 Inverter Status 001Eh 0 40000 LOW 001Fh 0 58000 HIGH 0020h Trip monitor 2 Current 0 1 A 0020h Output Current 0 01 A 0021h Trip monitor 2 Voltage 1 V 00...

Страница 25: ...1048h A038 0 999 0 01 Hz 1238h A038 Starting Frequency to 999 In the high frequency mode 10000 0 01 Hz Jogging stop selection 1049h A039 00 Free run stop 01 Deceleration stop 02 DC injection braking...

Страница 26: ...rgy saving operation 126Dh A085 00 Normal operation 01 Energy saving operation Energy saving response 1073h A086 0 1000 0 1 126Eh A086 0 1000 0 1 1074h A092 MSB 1274h A092 HIGH 1075h A092 LSB 1275h A0...

Страница 27: ...8 200 2000 0 1 Soft lock selection 10BCh b031 00 Data other than b031 cannot be changed when terminal SFT is ON 01 Data other than b031 and the specified frequency parameter cannot be changed when ter...

Страница 28: ...restart 01 Frequency matching restart 02 Frequency pull in restart Stop selection 10DAh b091 00 Deceleration Stop 01 Free run stop 135Eh b091 00 Deceleration stop 01 Free run stop Cooling fan control...

Страница 29: ...nary 3 05 CF4 Multi step speed setting binary 4 06 JG Jogging 07 DB External DC injection braking 08 SET 2nd control 09 2CH 2 step acceleration deceleration 11 FRS Free run stop 12 EXT External trip 1...

Страница 30: ...4 OD 05 AL 06 Dc 07 FBV 08 NDc 09 LOG 10 ODc Do not use 43 LOC 00 RUN During RUN 01 FA1 Constant speed arrival signal 02 FA2 Set frequency exceeded signal 03 OL Overload warning 04 OD Excessive PID de...

Страница 31: ...delay 1153h C144 1486h C130 Output terminal P1 OFF 1154h C145 1487h C131 Relay output ON delay 1157h C148 1490h C140 Relay output OFF delay 1158h C149 1491h C141 Motor capacity selection 1165h H003 15...

Страница 32: ...2019 0919 0919 I924 E1 01 Note Do not use this document to operate the Unit...

Отзывы: