Serial Interface Manual
OEL8000III Series Models K/X
Command: 302 Sensor Alarm History Report
Command Format:
Display: <SOH>I302SS
Computer: <SOH>i302SS
Typical Response Message, Display Format:
<SOH>
I30200
JUL 29, 2013 12:03 AM
OMNTEC MFG.
1993 POND ROAD
RONKONKOMA NEW YORK 11779
631-981-2001
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
13 Tank 1, Well: 1 JUL 25, 2013 04:12 PM Alarm
13 Tank 1, Well: 1 JUL 25, 2013 02:38 PM Alarm
14 Tank 1, LowLevel: 1 JUL 24, 2013 04:12 PM NO Reply
6 Tank 1, Caut_Low: 1 JUL 23, 2013 03:42 PM NO Reply
<ETX>
Typical Response Message, Computer Format:
<SOH>i302SSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. SS - Sensor Number (Decimal, 00 = all)
3. NN - Number of Alarms to follow
4. YYMMDDHHmm - Date and Time of Alarm
5. aaaa - Alarm type number:
0002 = Sensor Fuel Alarm
0005 = Sensor Water Alarm
0006 = Sensor Water Out Alarm
0007 = Sensor High Liquid Alarm
0008 = Sensor Low Liquid Alarm
0016 = LIQUID ALARM
0017 = VAPORS DETECTED
0018 = LEVEL ALARM
0019 = NO REPLY
0020 = BUS NO REPLY
0021 = LOW TEMP ALARM
0022 = HIGH TEMP ALARM
0023 = High Level Alarm
0024 = High/High Level Alarm
0025 = Em_High Level Alarm
0026 = High Level Alarm
0027 = High/High Level Alarm