9
Initial FuelCheck
®
SAE (standard) probe Installation
Low Pressure Installation
IMPORTANT: Note line pressure. If over 300 PSI (2000 kPa) follow instructions for high-
pressure installation.
NOTE - Make Initial measurement “A” before starting to install probe into pipeline.
1. Use Teflon tape or required sealing compo-
nents on the Insertion Tool Adapter and in-
stall Adapter on the Valve. Measure precise
length from pipeline to the to top of Insertion
Tool Adapter (Figure 3). Record this length
as measurement “
A”
.
2. Use ½ of the wall thickness on the pipeline to
ensure the tip of the probe is not intruding
into the pipeline. Calculate and record Probe
o-ring groove
machined into fitting
sensor element
safety stop
access valve
Insertion Tool Adapter
E N L A R G E D
C U T A W A Y
Process Insertion Fitting
SAE/MS STRAIGHT THREAD
Insertion Tool
Adapter
Valve
A
Figure 7
Probe Alignment
Figure 8
Insertion Valve measurement