4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518
www.omnimetrix.net ▪ 770-209-0012
IM-759 Rev. B
25-MAR-2019
Basler 2020 Wiring Installation
OMN Input Wire Color
Alarm Function
Basler Terminal
Red
Gen
3
Black
Gen Battery GND
2
Orange
Gen Running
Attach to switch side of
fuel solenoid. There is
no other Run relay
Blue
Common Alarm
54
Violet
Common Warning
56
Gray
n/a
n/a
Pink
Not in Auto
53
Tan
n/a
n/a
Yellow
n/a
n/a
Brown
n/a
n/a
Table 1
NOTE:
If 2-wire remote start is desired, use OmniMetrix White/Yellow and White/Brown wires across the
2-wire start terminals.
If you have any questions, please call OmniMetrix Tech Support at 770-209-0012 or email at
[email protected].