P a g e | 2
4295 Hamilton Mill Rd., #100
▪
Ph: 770-209-0012
www.omnimetrix.net
IM-1050-01
09-JUN-2020
LED Behavior:
The BLUE LED will illuminate at boot up (stay on). The LED will start blink rapidly, on/off every 1/2
second, once the modem is connected to an available tower. The LED will begin to blink more
slowly, three seconds on, three seconds off, once the modem has connected to the OmniMetrix
server. Note: The BLUE LED is an indication of network service. If it continues to stay illuminated
(on), please check the SIM card, antenna, and signal strength.
The Red LED illuminates approximately 20 seconds after the Blue LED illuminates. A solid Red LED
indicates the unit is trying to log into our server.
After approximately 20 seconds, Red LED turns off and the Green LED illuminates for 3 seconds.
This indicates the unit has logged into our server.
The Red LED or Green LED flashes after login: Short Green LED flashes indicate the monitor is
getting data; Long flashes of the Red LED indicate failure.
Signal Strength:
LED signal strength indication is provided at login and routinely during operation,
using the Red & Green LED’s as follows:
1.
The Red & Green LED’s flash rapidly for 2 seconds to indicate the beginning of the “Signal
Strength” routine.
2. Next, the LED(s) will stay fully illuminated 2 seconds to indicate the current signal strength:
a. Solid Red LED only = below 10
b. Solid Red & Green LED
’s = 10~60
c. Solid Green LED only = greater than 60.
3.
To complete the Signal Strength cycle, the Red & Green LED’s flash rapidly again for 2
seconds, then stop (end of cycle).
Kohler ADC-RES/DC-RET Wiring Table
OMX Wire
Function
Termination
Red
Power-In (+12 Vdc)
PF1
Black
Ground
0
Orange
Generator Running
70B
White/Yellow
Remote Start/Stop
TB1-3
White/Brown
Remote Start/Stop
TB1-4
If you have any questions, please call OmniMetrix Tech Support at 770-209-0012 or
email at [email protected]