TrueGuard-2
™
Kohler ADC-RES/DC-RET
Installation Guide
4295 Hamilton Mill Rd., #100
▪
Ph: 770-209-0012
www.omnimetrix.net
IM-1050-01
09-JUN-2020
TrueGuard-2
™
is for use on 12v systems only.
1. Unpack the monitor and antenna. The integrated cable includes
wires to power the monitor as well as wires for alarm inputs, relay
outputs and analog inputs. Inspect all components to verify there
is no shipping damage.
2. Place the antenna vertically on the outside cabinet of the
generator in an appropriate location that will not interfere with any
of the openings, and route the antenna cable into the area of the
generator control. It may be necessary to drill a hole in the
exterior housing and use the included plate to mount the antenna.
The antenna used for transmitting must be installed to provide a
separation distance of at least 20 cm from all persons and must
not transmit simultaneously with any other antenna transmitters.
BE SURE to provide a drip loop lower than the monitor to keep
water from running down the antenna cable into the monitor
connection.
3. Attach the monitor via its magnetic feet in an appropriate
location. Horizontal surfaces are best, but the unit may be
mounted vertically or even upside down if necessary
.
Note: If
mounted vertically, install the monitor with the cables down to
prevent water from entering the enclosure.
4. Instructions for wiring the monitor can be found in the table on
the following page.
5. Attach the antenna cable to the front of the monitor, and tighten
thumb tight.
6. Allow 15 minutes for the monitor to log into the network and
then call OmniMetrix at 770-209-0012 to confirm installation.
Access to machine data is through the OmniView
®
web
. Contact OmniMetrix for login
instructions and web training.
TrueGuard-2 System
TrueGuard-2 System
Kohler ADC-RES Control
Kohler DC-RET Control