28

 

 

(ill. 2) 
Crimping pliers PV-CZM... incl. locator and built-in 
crimping insert. 

Crimping range: 2,5 / 4 / 6 mm² (12 / 10 AWG) 
Type: PV-CZM-19100 
Order No. 32.6020-19100

 

 

(ill. 3) 
Open-end spanner PV-MS, 
1 Set = 2 pieces 

Order No.: 32.6024 

 

(ill. 4) 
PV-WZ-AD/GWD socket wrench insert to tighten 

Order No. 32.6006 

 

(ill. 5) 
PV-SSE-AD4 socket wrench insert to secure 

Order No. 32.6026 

 

(ill. 6) 
Test plug PV-PST 

Order No. 32.6028 

 

(ill. 7) 
Open-end spanner A/F 15 mm 

 

(ill. 8) 
Torque screwdriver A/F 12 mm 

 

Cable preparation

 

 

(ill. 9) 
Use  14-10AWG  (2.5-6mm

2

)  conductor  as  DC  cable. 

Dimension 

A

 3-6mm, 

b

 2.5-6mm

2

 

 

(ill. 10) 
Strip the cable end 

L

 with 6 mm to 7.5 mm of insulation. 

Содержание Omniksol-15k-TL2

Страница 1: ...User Manual V1 0 User Manual Installation Operation Omniksol 1k TL2 Omniksol 1 5k TL2 Omniksol 2k TL2 Omniksol 2 5k TL2 S Omniksol 3k TL2 S Omnik New Energy Co Ltd...

Страница 2: ......

Страница 3: ...pearance 14 4 3 Product Identification 15 4 4 Further Information 15 5 Installation 16 5 1 Safety 16 5 2 Mounting Instructions 17 5 3 Safety Clearance 18 5 4 Mounting Procedure 19 5 5 Safety lock 22 6...

Страница 4: ...k TL2 Omniksol 2k TL2 Omniksol 2 5k TL2 S Omniksol 3k TL2 S Please keep this user manual all time available in case of emergency 1 2 Symbols Used CAUTION CAUTION indicates a hazardous condition which...

Страница 5: ...ended to install or uninstall the Omnik Grid Tie Solar Inverter NOTICE Hereby qualified personnel means he she has the valid license from the local authority in Installing electrical equipment and PV...

Страница 6: ...ions including modification of product functionality of any form will affect the validation of warranty service Omnik may deny the obligation of warranty service accordingly DANGER DANGER due to elect...

Страница 7: ...shortly after operation Risk of damage due to improper modi cations Never modify or manipulate the inverter or other components of the system NOTICE Public utility only The PV inverter designed to fe...

Страница 8: ...NOT touch aluminum housing during operating An error has occurred Please go to Part 9 Trouble Shooting to remedy the error This device SHALL NOT be disposed of in residential waste Please go to Part...

Страница 9: ...7 3 Product Information 3 1 Overview Industrial Layout Excellent Heat Elimination...

Страница 10: ...ables more PV panels connected Wide MPP voltage range ensure high yield under various weather conditions High MPP tracking accuracy ensure the minimum power loses during converting Complete set of pro...

Страница 11: ...AC Apparent Power 1100VA 1650VA 2200VA Nominal AC Power cos phi 1 1000W 1500W 2000W Nominal Grid Voltage 220V 230V 240V 220V 230V 240V 220V 230V 240V Nominal Grid Frequency 50Hz 60Hz 50Hz 60Hz 50Hz 60...

Страница 12: ...4105 VDE 0126 1 1 RD1699 CEI0 21 C10 11 G83 2 UTE C15 712 1 AS4777 CQC Physical Structure Dimensions WxHxD 343x281x130mm Weight 11kg Environmental Protection Rating IP 65 According to IEC 60529 Cooli...

Страница 13: ...Connector Output AC Max AC Apparent Power 2750VA 3000VA Nominal AC Power cos phi 1 2500W 3000W Nominal Grid Voltage 220V 230V 240V 220V 230V 240V Nominal Grid Frequency 50Hz 60Hz 50Hz 60Hz Max AC Cur...

Страница 14: ...VDE 0126 1 1 RD1699 CEI0 21 C10 11 G83 2 UTE C15 712 1 AS4777 CQC Physical Structure Dimensions WxHxD 343x281x150mm Weight 13kg Environmental Protection Rating IP 65 According to IEC 60529 Cooling Con...

Страница 15: ...inside completeness for any visible external damage on the inverter or any accessories Contact your dealer if anything is damaged or missing Object Quantity Description A 1 Omnik inverter B 2 pairs DC...

Страница 16: ...14 4 2 Product Appearance Front Object Description A Removable front shield B LED light 3 pcs C Function keys for displays and setting 4 pcs D Monitoring LCD with backlighting Bottom A B C D A D B C...

Страница 17: ...tion such as type of the inverter as well as inverter specifications are specified on the side name plate The name plate is on the middle part of the right side of the inverter housing And the followi...

Страница 18: ...r Do NOT expose to rain and snow cover to enhance inverter life time The installation site MUST have good ventilation condition DANGER DANGER to life due to potential fire or electricity shock DO NOT...

Страница 19: ...es backwards For the convenience of checking the LCD display and possible maintenance activities please install the inverter at eye level Make sure the wall you selected is strong enough to handle the...

Страница 20: ...e following minimum clearances to walls other devices or objects to guarantee sufficient heat dissipation and enough space for pulling the electronic solar switch handle Direction Minimum clearance Ab...

Страница 21: ...19 5 4 Mounting Procedure 1 Mark 4 positions of the drill holes on the wall according to the wall mounting bracket in the carton box 150 228 Depth 50mm...

Страница 22: ...in the wall Then place four expansion tubes in the holes using a rubber hammer Next make 4 screws through the mounting holes in the bracket and then tighten the screws into the expansion tubes So far...

Страница 23: ...3 Check the 4 holes in the backside of the inverter Then lift the inverter carefully align the 4 holes in the inverter and the 4 hooks on the bracket and finally attach the inverter to the hooks sligh...

Страница 24: ...rner of the inverter as the picture showed below Recommended padlock dimension A Shackle Diameter 5 7 mm B Vertical Clearance 8 15 mm C Horizontal Clearance 12 20 mm Stainless solid hanger and secured...

Страница 25: ...R DANGER to life due to potential fire or electricity shock NEVER connect or disconnect the connectors under load NOTICE Electrical connections shall be carried out in accordance with the applicable r...

Страница 26: ...es or tin soldering 2 Check that all parts of AC connector are present Then slide hex nut onto the cable and insert the cable end through clamp ring 3 Insert the stripped N L and PE conductor terminal...

Страница 27: ...clamp ring with two click sound and then tighten the hex nut with tightening torque 4Nm 5 Finally connect the straight plug to the AC terminal on inverter Pay attention to the polarity of the termina...

Страница 28: ...elf assembly parts and tools other than those stated by MC are used or if the preparation and assembly instructions described here are disregarded then neither safety nor compliance with the technical...

Страница 29: ...ed permanently under water Do not lay the MC PV connectors on the roof surface See the MC catalogue 2 solar lines for technical data and assembled parts PV Female cable coupler PV Male cable coupler O...

Страница 30: ...6024 ill 4 PV WZ AD GWD socket wrench insert to tighten Order No 32 6006 ill 5 PV SSE AD4 socket wrench insert to secure Order No 32 6026 ill 6 Test plug PV PST Order No 32 6028 ill 7 Open end spanne...

Страница 31: ...until the insulation comes up against the crimp insert Completely close the crimping pliers ill 14 Visually check the crimp ill 15 Insert the crimped on contact into the insulator of the male or fema...

Страница 32: ...operly by pulling on the cable coupler 6 4 Communication and Monitoring Device There are 2 RJ45 plugs in the bottom side of the Omnik inverter as the following figure These 2 RJ45 plugs are used for m...

Страница 33: ...LED light Green RUN C LED light Red FAULT D UP key E DOWN key F ESC key G ENTER key The LCD panel is integrated in the front lid of the inverter so it is easy for user to check and set the data In add...

Страница 34: ...ch and Deutsch are available for display NOTICE You need to confirm that you choose the right country safety to ensure that compliance with local standards NOTICE The power supply of display module is...

Страница 35: ...us Display as Waiting XXX XXX refers to the countdown time will display 1 3 numbers 2 Flash status Display as Flash 3 Fault status Display as Fault XX XX refers to error code will display 1 2 numbers...

Страница 36: ...of the 2 input PV panel System operation interface 4 This interface displays the voltage and frequency of grid and the current which inverter outputs to the grid System operation interface 5 This int...

Страница 37: ...nd key ESC ENTER in system operation interface 1 for 3 seconds Safety Italy in the screen flickers After confirm to enter password dialog box appears The default password is 654321 After entering the...

Страница 38: ...eIsla Czech Slovak Holland Sweden Bulgari France Brazil EngG592 Holl16A SAfrica This safety information will be arranged in 4 lines i e there will be 4 safety information displayed in the same interfa...

Страница 39: ...37 2 AC grid information 3 Inverter s Model information 4 Inverter s SN Information...

Страница 40: ...38 5 Inverter s master CPU information 6 Inverter s slave CPU information 7 Inverter s display module version information...

Страница 41: ...by UP and DOWN key in system operation interface 1 While Error flickers confirm to enter the Error record mode Interface number of the Error record mode is unfixed it ranges from 0 to 9 interfaces No...

Страница 42: ...Set flickers confirm to enter the Set mode The Set mode is operated with 2 levels of menu There are five items in the sub menu Time Data Password Language and WiFi The items are shown as following pi...

Страница 43: ...flickers confirm to enter the language option list Choose the target language the corresponding language flickers English Dutch and Deutsch are available for displaying Click ENTER to save data and ba...

Страница 44: ...fied interface Input 6 figure passwords check correctness and enter the modified mode Save password after the end of input Back to two level menu mode after saving the password Setting Time In the Set...

Страница 45: ...OWN key to change the value Setting Date In the Set mode choose Date by UP and DOWN key as shown in the picture While Date field flickers confirm to enter the inverter Date Setting mode There are day...

Страница 46: ...e failure PV Voltage Fault Input voltage too high Over Temp Fault Temperature abnormal Isolation Fault Isolation failure Relay1 Fault Relay2 Fault Output relay failure Current DC Offset Output DC inje...

Страница 47: ...rical equipment that has reached the end of its life must be collected separately and returned to an approved recycling facility Any device that you no longer required must be returned to your dealer...

Страница 48: ...Check grid usability 4 If grid is ok and the problem persists maybe the fuse in the inverter is open please call service Over Temp Fault 1 The internal temperature is higher than specified normal valu...

Страница 49: ...Fault 9 No Utility 10 Current Fault 11 Bus Voltage Fault 12 B12 13 Over Temp Fault 14 Auto Test fail 15 PV Voltage Fault 16 Fan Fault 17 Master Grid Volt Fault 18 Isolation Fault 19 Current DC Offset...

Страница 50: ...t Form of electricity supplied by Utility Company DC Direct Current Form of electricity generated by PV modules VDE 0126 1 1 German standard for establishing suitability for Grid Connection of the Inv...

Страница 51: ...86 512 6295 6676 Fax 86 512 6295 6682 Email info omnik solar com www omnik solar com Omnik German Service Center Omnik GmbH Forsthausstr 8A 65479 Raunheim Tel 49 179 9762 654 Email service de omnik s...

Отзывы: