Omniflex MAXIFLEX 1000 SERIESM1102A Скачать руководство пользователя страница 3

© Copyright Omniflex                                               Data subject to change without notice  

                             M1102A Rev. 11.04.03 

 

Figure 2 : Layout of a Maxiflex 7 I/O Base 

 

 
Mechanical Installation 

DAMAGE WILL RESULTO THE EQUIPMENT IF THE PSU MODULE IS PLUGGED INTO ANY 
POSITION OTHER THAN THE PSU POSITION ON THE BASE. 
 
REMOVE THE POWER TO THE PSU MODULE BEFORE INSERTING THE PSU MODULE INTO, 
OR REMOVING IT FROM THE BASE. 

 

Refer to Figure 2 for the layout of the Maxiflex base. 
 

Electrical Installation 

The following electrical connections are required to the unit: 
1. 

DC Power 

2. 

Earth 

Refer to Figure 1 for the external connections required. 
 

Field Test Procedure 

The only test that is possible is observation of the two LEDs.  Refer to the Fault/Symptom Chart 
for diagnosis using the two LEDs. 
 

Table 3 : Fault/Symptom Chart 

 

LED 

Action 

Possible Cause 

Solution 

Power 

Off 

5V and 12V supplies faulty 

Thoroughly check the PSU. 

Overvoltage on either the 5V 

dc and/or the 12V dc 

Repair the PSU. 

Shutdown 

On 

Noise-triggered shutdown 

Reset the supply by temporarily 
switching the 24V off. 

Blown fuse 

Replace blown fuse. 

No primary supply 

Check whether 24V is present. 

Outputs short-circuited 

Remove PSU from Maxiflex 
base and re-check with terminal 
block connected 

Both 

Off 

PSU faulty 

Thoroughly check the PSU. 

Отзывы: