If the TEST button is depressed - lamp No. 4 flashes continuously.
If any other lamp flashes continuously, then the unit has detected a fault and must be returned
to the factory for service.
If a new alarm occurs while the Omni8/16C is in this test routine, the unit will immediately
revert to its normal mode of operation and will deal with the alarm state according to the pre-
selected alarm sequence.
It is possible under some circumstances to continue to operate the Omni8/16C even after a fault has
been detected. The table below will assist in diagnosing the fault found.
Table 6-1 Fault diagnosis during Circuit Test
Display
Window No.
FAULT SYMPTOM
POSSIBLE CAUSE
1
FLASHING
during “Marching Sequence”
SIL pushbutton held down, or
stuck in ON state
STEADY ON during “Marching Sequence”, and stays
ON during “Blank” display period.
Window No. 1 has lamp output
circuit fault.
STEADY
OFF
during “Marching Sequence”, and stays
OFF during “Blank” display period.
Window No. 1 has lamp failure or
output circuit fault.
2
FLASHING
during “Marching Sequence”
ACK pushbutton held down, or
stuck in ON state (this condition
must have been present BEFORE
the CCT. TEST mode was
initiated)
STEADY ON during “Marching Sequence”, and stays
ON during “Blank” display period.
Window No. 2 has lamp output
circuit fault.
STEADY
OFF
during “Marching Sequence”, and stays
OFF during “Blank” display period.
Window No. 2 has lamp failure or
output circuit fault.
3
FLASHING during “Marching Sequence”
RESET pushbutton held down, or
stuck in ON state.
STEADY ON during “Marching Sequence”, and stays
ON during “Blank” display period
Window No. 3 has lamp output
circuit fault.
STEADY
OFF
during “Marching Sequence”, and stays
OFF during “Blank” display period
Window No. 3 has lamp failure or
lamp output circuit fault.
4
FLASHING
during “Marching Sequence”
TEST pushbutton held down, or
stuck in ON state.
STEADY ON during “Marching Sequence”, and stays
ON during “Blank” display period.
Window No. 4 has lamp output
circuit fault.
STEADY
OFF
during “Marching Sequence”, and stays
OFF during “Blank” display period.
Window No. 4 has lamp failure or
lamp output circuit fault.