“Empty/Full” Calibration
Perform the calibration in the fuel, in which the Omnicomm LLS-Ex 5 fuel level sensor will
operate.
1. Fill the measuring container with fuel
2. Immerse the Omnicomm LLS-Ex 5 sensor in the fuel to the full length of the
measuring probe
3. Wait for the green “Stabilized” indicator to appear.
Press “Full” to set the value corresponding to a full tank
4. Take the Omnicomm LLS-Ex 5 sensor out of the container and allow the fuel to flow
down the measuring piece for 1 minute. Press “Empty” to set the value corresponding
to an empty tank
5. Press the “Record into device” button
15