Installation, Operation, And Service Instructions
7
Figure 2
– Wiring Diagram
1. Wire 240V into main electrical box mounted on burner backside of heater cabinet with separate
circuit
20-amp protection using 12-gauge wire.
Connect power line to black wire and all whites
(NUETRAL or COMMON) together.
IMPORTANT,
Connect ground wire to ground mounting point
in main junction box (green screw).
2. Connect wires from main junction box to remote oil pump power. Yellow to yellow and neutral
common white to white.
3. Wire low voltage thermostat into “T” marked terminals on oil primary control on burner. (Box on
burner gun assembly with red reset button). (figure 3).
All unit heaters are designed with a condenser-type pressure propeller fan for air deliver, and
have been successfully field ducted. (See Specifications) call factory for further assistance if
needed.
Installation and use of this used oil burning appliance shall be in accordance with the
standard for the Installation of Oil Burning Equipment
– ANSI/NFPA 31 – 1987, and
National Electric Code
– ANSI/NFPA 70 – 1990 and the requirements of the inspection
authorities having jurisdiction.
DUCTING
OIL BURNER
WARNING