background image

 

Installation, Operation, And Service Instructions

 

 

 

 

 
Figure 2

 

– Wiring Diagram 

 

1. Wire 240V into main electrical box mounted on burner backside of heater cabinet with separate 
circuit 

20-amp protection using 12-gauge wire. 

Connect power line to black wire and all whites 

(NUETRAL or COMMON) together. 

IMPORTANT,

 Connect ground wire to ground mounting point 

in main junction box (green screw).   
 
2.  Connect wires from main junction box to remote oil pump power.  Yellow to yellow and neutral 
common white to white. 
 
3. Wire low voltage thermostat into “T” marked terminals on oil primary control on burner. (Box on 
burner gun assembly with red reset button). (figure 3). 
 
 

 

 
All unit heaters are designed with a condenser-type pressure propeller fan for air deliver, and 
have been successfully field ducted.  (See Specifications) call factory for further assistance if 
needed.   

 

 

 

 

Installation  and  use  of  this used  oil  burning  appliance  shall  be  in  accordance  with  the 
standard  for  the  Installation  of  Oil  Burning  Equipment 

–  ANSI/NFPA  31  –  1987,  and 

National  Electric  Code 

–  ANSI/NFPA 70  – 1990  and the requirements of the inspection 

authorities having jurisdiction.

 

DUCTING 

OIL BURNER  

WARNING 

Содержание OWH-150

Страница 1: ...tructions Manual 240v Thank you and congratulations on your purchase of an Omni Waste Oil Fired Heater You have selected a high quality precision engineered piece of equipment designed to give you man...

Страница 2: ...n this manual apply to the installation operation and service of Omni Waste oil fired heaters The following instructions should be carefully followed for obtaining the best possible installation opera...

Страница 3: ...eneral Maintenance Requirements Identical to any gas or oil furnace without adequate draft over the fire the combustion gases cannot escape the furnaces The flame will lengthen resulting in an overhea...

Страница 4: ...herein are based on the latest information available at the time of publication approval Econo Heat reserves the right to make changes at any time without notice in materials specifications and models...

Страница 5: ...ack if the draft up the stack exceeds 08 Draft up the stack must be 04 to 06 inches of water column Check with draft meter between the top of the heater and damper The over fire draft should be a mini...

Страница 6: ...to the inside supply tank is acceptable and available from Econo Heat 4 The fuel supply pump included with heater is to be mounted at tank level or below figure 1 This pump turns slowly requiring a nu...

Страница 7: ...al common white to white 3 Wire low voltage thermostat into T marked terminals on oil primary control on burner Box on burner gun assembly with red reset button figure 3 All unit heaters are designed...

Страница 8: ...lock 240v Photo Eye Flame Sensor Transformer Igniter Springs 240v Pre Heater Control Circuit Board Electrical Terminal Block Igniter Transformer 240v Air Band combustion air supply adjustment Oil Prim...

Страница 9: ...on And Service Instructions 9 Figure 5 Oil Burner Front View Figure 6 Oil Pump Diagram Oil Valve 240v Flame Cone Nozzle Electrodes Burner Motor 240v Oil Inlet Oil Outlet Igniter Transformer 240v Oil P...

Страница 10: ...air compressor figure 3 is mixed with the oil prior to spraying out the nozzle similar to fuel injection by breaking up the oil droplets into a finer mist or spray atomization Electrodes mounted just...

Страница 11: ...trol Circuit Board figure 4 Precisely controls temperature of the Oil Pre Heater Block and controls safety feature of not allowing burner to energize until oil has established operating thermo setpoin...

Страница 12: ...re the thermostat is turned off apply power to the burner Switch burner main power switch to ON position After allowing the oil pre heater time to establish temperature setpoint approximately 5 minute...

Страница 13: ...insure all air is removed IMPORTANT When fully purged and flame is established remove temporarily jumpers on F terminals of the Oil Primary to allow safety features of the unit to operate properly 13...

Страница 14: ...hould be check periodically and at time of installation to be sure they are set as noted in the following dimensional drawing Swing burner clean out door back for inspection figure 5 10 and 11 CAUTION...

Страница 15: ...10 Electrode Adjustment Detail Figure 11 Pre Heater Block Detail Removed From Burner for Clarity Figure 12 Combustion Chamber and Heat Exchanger Cleanout Door Models OWH 250 350 500 Nozzle Electrodes...

Страница 16: ...in On Filter above Pancake Style Filter below Remove 4 bolts for access to strainer filter CAUTION must be careful not to destroy the inner gasket during removal of the housing Filter Housing Spin On...

Страница 17: ...replace Check filter clean if needed 4 Reduced air pressure Gauge may be bad Replace gauge cannot increase Intake filter muffler is plugged Remove Clean with carburetor cleaner with dust or dirt dry t...

Страница 18: ...aft Flame end Swing open burner door and clean ash build up from flame Need to reset primary cone may have ash end cone See Figure 5 8 Flame too small Increase pump motor speed See Figure 7 9 Proper d...

Страница 19: ...rated or has been misused 5 Wiring not in accordance with diagram furnished with unit heater 6 Unit heater is operated in the presence of chlorinated vapors 7 Air through unit heater is not in accorda...