4
Installation, Operation, And Service Instructions
MODEL
OWH-150
OWH-250
OWH-350
OWH-500
BTU’S/HR INPUT
150,000
250,000
350,000
500,000
BTU’S/HR OUTPUT
120,000
215,000
300,000
410,000
GALLONS PER HOUR
1.0
1.75
2.4
3.4
VOLTAGE REQUIREMENTS
115
115
115
115
AMPS FULL LOAD with
Pump
14.6
17.0
18.7
23.5
FAN MOTOR HP
1/4
1/3
2 @ 1/4 each
2 @ 1/3 each
FAN MOTOR RPM
1075
1075
1075
1075
FAN DIA/PITCH
18/36
24/18
18/36
24/18
CFM (FREE AIR)
3762
4466
6275
9001
CFM W/ DUCTWORK at 100
FT
1380
2000
1600
3701
EFFECTIVE AIR FLOW
50 FT
60 FT
70 FT
100 FT
FLUE SIZE
8”
8”
8”
10”
WEIGHT W/ BURNER
240 LBS
365 LBS
400 LBS
660 LBS
SHIPPING WEIGHT
375 LBS
535 LBS
575 LBS
725 LBS
DIMENSIONS L/W/H
42-22-25 ½
44-30-28 ½
54-29 ½-28 ½
72-38-34 ½
SHIPPING DIMENSIONS
L/W/H
64 ½-30-49
64 ½-39-49
76-38-49
92-44-50
Notes:
1.
All illustrations and specifications contained herein are based on the latest information
available at the time of publication approval. Econo Heat reserves the right to make
changes at any time without notice, in materials, specifications, and models or to
discontinue models.
2.
These appliances are designed for commercial or industrial use only. Installation and use
of this waste-oil burning appliance shall be in accordance with the Standard for the
Installation of Oil Burning Equipment-ANS/NFPA 31-1987, and National Electric Code -
ANSI/NFPA 70-1990 and the requirements of the inspection authorities having jurisdiction.
3.
Output depends on BTU content of oil used.
4.
Atomizing Air Pressure for all fuels 10 P.S.I.
5.
Furnace not to be used with air filters.
6.
Intended maximum outlet air temp. 200 degrees F. (93 degrees C) or less.
7.
Clearance from combustible materials on all models not to be less than:
TOP-
6”
BOTTOM-
18”
SIDES-
18”
REAR-
18”
FRONT-
48”
FLUE PIPE-
18”
Mounting Dimensions:
SPECIFICATIONS
A
B
Heater
(Top)
MODEL A B
OWH-150
35 ½” 20”
OWH-250
35 ½” 22 ¼”
OWH-350
47 ¾” 22 ¼”
OWH-500