RELIEF VALVE LEAKS CONSTANTLY:
• Check system pressure. With system hot, pressure should be in the 20 psi to 25 psi range,
not to exceed 25 psi. With system cold, pressure should be in the 12-14 psi range. If pressure
is over these ranges, then suspect the pressure reducing fill valve or the expansion tank.
A diaphragm tank may be too small, may have a ruptured diaphragm (this would cause
a very sharp rise in pressure as system water heats up and a sudden opening of the relief
valve) or may be over-pressurized. A closed type expansion tank may be undersized, may
be improperly piped to the boiler, may be water logged.
• Relief valve may be defective, or it may have foreign material lodged on the seat.
OMNI Waste Oil Boiler Limited Warranty
EconoHeat (manufacturer) warrants to the purchaser of Unit Heaters listed above will be free
from defects in materials and workmanship for the durations specified below, which duration
begins on the date of delivery to the customer. Customer is responsible for maintaining proof
of date of delivery.
If return is deemed necessary for warranty evaluation and determination of repair or
replacement, unit heater is to be sent to the factory with freight prepaid. EconoHeat reserves
the right to determine appropriate action for repair or replacement.
No parts will be accepted by EconoHeat without RA# (return authorization number) clearly marked
on outside of shipping package. Obtaining RA# requires model and serial numbers, description
of part being replaced and nature of defect. Call factory to receive RA#.
Warranty Covers:
• Boiler cast iron jacket, one (1) year (parts only)
• Stainless steel combustion tube Insert, five (5) years limited (part only)
• Oil heater block, twenty (20) years (parts only)
• Oil heater block controller PCB, three (3) years (parts only)
• All other components, one (1) year (parts only)
This warranty is void if:
• Warranty registration card is not returned within sixty (60) days of purchase
• Any part or component subject to abuse or altered from original manufactures specifications
• Installation not in accordance with instructions
• Has not been properly maintained, operated or has been misused
• Wiring not in accordance with diagram furnished with unit heater
• Unit heater is operated in the presence of chlorinated vapors
• Air through unit heater is not in accordance with rating plate and specifications
• Target plate or clean out door warped/discolored from excessive heat